高电压技术
高電壓技術
고전압기술
HIGH VOLTAGE ENGINEERING
2009年
8期
1994-1999
,共6页
梁可道%米彦%李成祥%姚陈果%孙才新%田鹏
樑可道%米彥%李成祥%姚陳果%孫纔新%田鵬
량가도%미언%리성상%요진과%손재신%전붕
脉冲磁场%测量%传感器%探头%电磁干扰%变电站
脈遲磁場%測量%傳感器%探頭%電磁榦擾%變電站
맥충자장%측량%전감기%탐두%전자간우%변전참
pulsed magnetic field%measurement%sensor%probe%electromagnetic interference(EMI)%substation(2009CB724506).Project Supported by National Basic Research Program of China (973 Program)(2009CB724506).
变电站内存在具有ns级上升沿且幅值较高、频带较宽的快速瞬态电磁脉冲,以辐射和传导的方式干扰保护与控制等二次设备.为了评估变电站内电磁干扰及防护措施对干扰抑制效果的问题,基于法拉第电磁感应定律,研制了一套可用于测量高幅值、宽频带磁脉冲的ns级脉冲磁场传感器,并分析了其基本原理、幅频特性、灵敏度、方波磁场的幅值响应和测量干扰,阐述了其设计原则及应注意的问题.通过模拟电磁脉冲对其标定与测试,结果表明,此传感器的灵敏度为703.42 V/T,频带为400 kHz~100 MHz,满足变电站内瞬态脉冲磁场测量的要求.
變電站內存在具有ns級上升沿且幅值較高、頻帶較寬的快速瞬態電磁脈遲,以輻射和傳導的方式榦擾保護與控製等二次設備.為瞭評估變電站內電磁榦擾及防護措施對榦擾抑製效果的問題,基于法拉第電磁感應定律,研製瞭一套可用于測量高幅值、寬頻帶磁脈遲的ns級脈遲磁場傳感器,併分析瞭其基本原理、幅頻特性、靈敏度、方波磁場的幅值響應和測量榦擾,闡述瞭其設計原則及應註意的問題.通過模擬電磁脈遲對其標定與測試,結果錶明,此傳感器的靈敏度為703.42 V/T,頻帶為400 kHz~100 MHz,滿足變電站內瞬態脈遲磁場測量的要求.
변전참내존재구유ns급상승연차폭치교고、빈대교관적쾌속순태전자맥충,이복사화전도적방식간우보호여공제등이차설비.위료평고변전참내전자간우급방호조시대간우억제효과적문제,기우법랍제전자감응정률,연제료일투가용우측량고폭치、관빈대자맥충적ns급맥충자장전감기,병분석료기기본원리、폭빈특성、령민도、방파자장적폭치향응화측량간우,천술료기설계원칙급응주의적문제.통과모의전자맥충대기표정여측시,결과표명,차전감기적령민도위703.42 V/T,빈대위400 kHz~100 MHz,만족변전참내순태맥충자장측량적요구.
The switching operation in the primary circuit will cause the electromagnetic transient process in the highvoltage bus,which produces the transient voltage in the secondary side of the potential transformer and consequently causes the interference in the secondary circuit.All the interferences can cause problems like misoperation,data loss,damage of equipments etc.In order to evaluate the transient electromagnetic interference in substations and to analyze the contributions of shielding measures to the interference,based on Faraday's law of electromagnetic induction,we developed a pulsed magnetic field sensor which could be used to measure fast transient magnetic pulses with ns rise time,high amplitude,broadband.The sensor basic principles,amplitude frequency characteristics,sensitivity,amplitude response for square wave magnetic and interference in measurements were analyzed, calibrated and tested by a electromagnetic pulse simulator,and its design approach and problems that should be paid attention to during development were also discussed.The results show that this sensor' sensitivity is 703.42 V/T.and its frequency band is 400 kHz~1 00 MHz.That is to say it can meet the requirements of measurement of transient pulsed magnetic field in substations.