替代制冷剂%翅片管蒸发器%相对湿度%压降
替代製冷劑%翅片管蒸髮器%相對濕度%壓降
체대제랭제%시편관증발기%상대습도%압강
Alternative refrigerants%Finned-tube evaporator%Relative humidity%Pressure drop
基于换热器几何结构参数以及流路布置等相同的3HP商用空调,在空调工况下,研究了相对湿度对R22替代制冷剂R407C、R410A、R32以及R290在蒸发器内的流动和传热性能的影响规律.研究表明:在一定的条件下,增加环境相对湿度,这五种制冷剂对应蒸发器换热量、压降和质量流量均增加,其中R407C蒸发器换热量最大,R290和R32蒸发器压降和制冷剂质量流量均小于R22蒸发器.在低湿度环境下(约20-30%相对湿度),显热换热占主导因素.随着相对湿度的增加,显然换热减少,潜热换热增强且起主导因素.在满足换热量的要求下,R290在协调压降与质量流量具有一定的优势且满足现行工质替代理念, 可以作为现有商用空调的环保型替代工质.
基于換熱器幾何結構參數以及流路佈置等相同的3HP商用空調,在空調工況下,研究瞭相對濕度對R22替代製冷劑R407C、R410A、R32以及R290在蒸髮器內的流動和傳熱性能的影響規律.研究錶明:在一定的條件下,增加環境相對濕度,這五種製冷劑對應蒸髮器換熱量、壓降和質量流量均增加,其中R407C蒸髮器換熱量最大,R290和R32蒸髮器壓降和製冷劑質量流量均小于R22蒸髮器.在低濕度環境下(約20-30%相對濕度),顯熱換熱佔主導因素.隨著相對濕度的增加,顯然換熱減少,潛熱換熱增彊且起主導因素.在滿足換熱量的要求下,R290在協調壓降與質量流量具有一定的優勢且滿足現行工質替代理唸, 可以作為現有商用空調的環保型替代工質.
기우환열기궤하결구삼수이급류로포치등상동적3HP상용공조,재공조공황하,연구료상대습도대R22체대제랭제R407C、R410A、R32이급R290재증발기내적류동화전열성능적영향규률.연구표명:재일정적조건하,증가배경상대습도,저오충제랭제대응증발기환열량、압강화질량류량균증가,기중R407C증발기환열량최대,R290화R32증발기압강화제랭제질량류량균소우R22증발기.재저습도배경하(약20-30%상대습도),현열환열점주도인소.수착상대습도적증가,현연환열감소,잠열환열증강차기주도인소.재만족환열량적요구하,R290재협조압강여질량류량구유일정적우세차만족현행공질체대이념, 가이작위현유상용공조적배보형체대공질.
Based on the same geometrical parameters, circuitry arrangement and so on, the characteristics of alternative refrigerants R407C、R410A、R32 and R290 to R22 in finned-tube heat evaporator of 3HP commercial air conditioning system are investigated under air conditioning operating condition.The effects of different relative humidity on the flow and heat transfer performance of evaporators are analyzed. The results show that all of the heat flux、pressure drop and the mass flow rate of the five alternative refrigerants increase with increased relative humidity of the ambient under certain conditions. R407C obtains the largest heat flux. Both the pressure drop and the mass flow rate of refrigerants R290 and R32 are lower than that of R22. Under the lower relative humidity ranged from 20% to 30%, the heat flux of sensible heat becomes the dominant factor governing the evaporator capacity. Both the sensible heat and latent heat increase with increased relative humidity, and the heat flux of latent heat acts as the dominant factor. Overall, when the heat flux of the system is contented, the results demonstrate that R290 has the particular advantages in terms of harmonizing the pressure drop with the mass flow rate, and is also in line with the present ideas of alternative refrigerants. It can be used as environment friendly alternative refrigerant for commercial air-conditioning.