中国电机工程学报
中國電機工程學報
중국전궤공정학보
ZHONGGUO DIANJI GONGCHENG XUEBAO
2011年
34期
192-197
,共6页
尤飞%陈海翔%张林鹤%张云%周建军%朱霁平
尤飛%陳海翔%張林鶴%張雲%週建軍%硃霽平
우비%진해상%장림학%장운%주건군%주제평
跳闸%空气间隙%高压输电线路%木垛火%平均击穿场强
跳閘%空氣間隙%高壓輸電線路%木垛火%平均擊穿場彊
도갑%공기간극%고압수전선로%목타화%평균격천장강
flashover%air gap%high-voltage transmission lines%wood crib fire%average breakdown field strength
为确定山火作用下高压输电线路间空气间隙的击穿特性及机制,利用模拟实验研究了工频高压作用下单股、双分裂和四分裂模拟导线与地之间间隙在木垛火作用下的击穿特性,并与空气中间隙的击穿特性进行了比较。实验结果表明木垛火焰可显著降低高压导线的平均击穿场强。高压导线在木垛火稳定燃烧期火焰作用下和在熄灭阶段火羽流作用下的平均击穿场强与空气中相应值的比值分别为27.3%~33.5%和39.4%~48.4%(实验值),均分别低于根据木垛火高温影响平均击穿场强公式计算所得稳定火焰中和熄灭火焰中的相应比值,即37.4%和49.8%(计算值)。这表明木垛火击穿实验中火焰的高温效应是降低平均击穿场强的主要原因,而火焰的电离作用相对次要。
為確定山火作用下高壓輸電線路間空氣間隙的擊穿特性及機製,利用模擬實驗研究瞭工頻高壓作用下單股、雙分裂和四分裂模擬導線與地之間間隙在木垛火作用下的擊穿特性,併與空氣中間隙的擊穿特性進行瞭比較。實驗結果錶明木垛火燄可顯著降低高壓導線的平均擊穿場彊。高壓導線在木垛火穩定燃燒期火燄作用下和在熄滅階段火羽流作用下的平均擊穿場彊與空氣中相應值的比值分彆為27.3%~33.5%和39.4%~48.4%(實驗值),均分彆低于根據木垛火高溫影響平均擊穿場彊公式計算所得穩定火燄中和熄滅火燄中的相應比值,即37.4%和49.8%(計算值)。這錶明木垛火擊穿實驗中火燄的高溫效應是降低平均擊穿場彊的主要原因,而火燄的電離作用相對次要。
위학정산화작용하고압수전선로간공기간극적격천특성급궤제,이용모의실험연구료공빈고압작용하단고、쌍분렬화사분렬모의도선여지지간간극재목타화작용하적격천특성,병여공기중간극적격천특성진행료비교。실험결과표명목타화염가현저강저고압도선적평균격천장강。고압도선재목타화은정연소기화염작용하화재식멸계단화우류작용하적평균격천장강여공기중상응치적비치분별위27.3%~33.5%화39.4%~48.4%(실험치),균분별저우근거목타화고온영향평균격천장강공식계산소득은정화염중화식멸화염중적상응비치,즉37.4%화49.8%(계산치)。저표명목타화격천실험중화염적고온효응시강저평균격천장강적주요원인,이화염적전리작용상대차요。
In order to determine the influences of forest fire on the flashover property and mechanism of air gap under high voltage transmission lines,the flashover characteristics of simulative AC high-voltage transmission lines(single-bundle conductor,double-bundle conductor and four-bundle conductor) under the effect of wood crib fire were investigated and compared with the gap breakdown characteristics in air.Results show the average breakdown field strengths of transmission lines are remarkably decreased by wood crib flame.The measured ratio values of the average breakdown field strengths of gap in stable flame and in extinguishing flame to those in air(27.3%~33.5% and 39.4%~48.4%,respectively) are found to be lower than the calculated ratio values(37.4% and 49.8%,respectively),which are obtained by the proposed formulas that calculate the breakdown field strength under the high temperature field of wood crib fire.These results indicate that high flame temperature is the primary factor while flame ionization is secondary contributing to the reduction of breakdown filed strength.