电网技术
電網技術
전망기술
POWER SYSTEM TECHNOLOGY
2012年
2期
176-181
,共6页
王巨丰%曲振旭%苏浩益%黄维%刘儒
王巨豐%麯振旭%囌浩益%黃維%劉儒
왕거봉%곡진욱%소호익%황유%류유
35%kV输电线路%雷击过电压%灭弧防雷间隙%电弧模型
35%kV輸電線路%雷擊過電壓%滅弧防雷間隙%電弧模型
35%kV수전선로%뢰격과전압%멸호방뢰간극%전호모형
35 kV overhead transmission line%lighting overvoltage%air-blast arc-quenching gap%arc model
针对我国南方部分地区35kV架空输电线路雷击事故严重的情况,设计一种基于“疏导型”防雷理念和“气吹灭弧”相结合的灭弧防雷间隙,该间隙在输电线路发生雷击时能优先于绝缘子串闪络,将雷电流导入大地的同时熄灭工频续流。通过小电流灭弧特性试验和仿真建立的灭弧防雷间隙的PSCAD仿真计算模型,针对广西大化县35kV架空输电线路的仿真计算结果和实际运行情况表明,输电线路安装灭弧防雷间隙可有效抑制雷击过电压,降低线路的雷击跳闸率。
針對我國南方部分地區35kV架空輸電線路雷擊事故嚴重的情況,設計一種基于“疏導型”防雷理唸和“氣吹滅弧”相結閤的滅弧防雷間隙,該間隙在輸電線路髮生雷擊時能優先于絕緣子串閃絡,將雷電流導入大地的同時熄滅工頻續流。通過小電流滅弧特性試驗和倣真建立的滅弧防雷間隙的PSCAD倣真計算模型,針對廣西大化縣35kV架空輸電線路的倣真計算結果和實際運行情況錶明,輸電線路安裝滅弧防雷間隙可有效抑製雷擊過電壓,降低線路的雷擊跳閘率。
침대아국남방부분지구35kV가공수전선로뢰격사고엄중적정황,설계일충기우“소도형”방뢰이념화“기취멸호”상결합적멸호방뢰간극,해간극재수전선로발생뢰격시능우선우절연자천섬락,장뇌전류도입대지적동시식멸공빈속류。통과소전류멸호특성시험화방진건립적멸호방뢰간극적PSCAD방진계산모형,침대엄서대화현35kV가공수전선로적방진계산결과화실제운행정황표명,수전선로안장멸호방뢰간극가유효억제뢰격과전압,강저선로적뢰격도갑솔。
In allusion to serious situation that the faults caused by lightning stroke frequently occur in 35 kV overhead transmission lines in part of South China, an air-blast arc-quenching gap based on the "scatter" thinking of lightning protection is designed. When lightning strikes on overhead transmission line, the designed air-blast arc-quenching gap can flashover prior to the flashover of insulator string and the power frequency afterflow will be quenched while the lightning current is being flowed into ground via the designed gap. Based on the testing data from small-current arc-quenching property tests of the designed gap and simulation results, a-PSCAD model of the designed gap is built, and the simulation results of 35 kV overhead transmission line located in Dahua county, the Guangxi Zhuang Autonomous Region as well as the actual operation effect of the gap show that lightning overvoltage can be effectively suppressed by installing the designed gap on 35 kV overhead transmission lines, thus the lightning trip-out rate of overhead ';transmission line can be decreased.