高电压技术
高電壓技術
고전압기술
HIGH VOLTAGE ENGINEERING
2011年
9期
2149-2155
,共7页
尤少华%刘云鹏%律方成%万晓东%万启发%吴湘源
尤少華%劉雲鵬%律方成%萬曉東%萬啟髮%吳湘源
우소화%류운붕%률방성%만효동%만계발%오상원
特高压(UHV)%同塔双回试验线段%电晕笼%雨天%电晕损失%有效电晕损失
特高壓(UHV)%同塔雙迴試驗線段%電暈籠%雨天%電暈損失%有效電暈損失
특고압(UHV)%동탑쌍회시험선단%전훈롱%우천%전훈손실%유효전훈손실
ultra high voltage(UHV)%double circuits test line on the same tower%corona cage%rain%corona loss%reduced corona loss
为了获得特高压交流同塔双回输电线路雨天电晕损失评估的关键数据,采用特高压交流同塔双回试验线段、特高压电晕笼两种试验手段,应用光纤数字化测量方法监测雨天气象条件下特高压交流同塔双回试验线段电晕损失,测量特高压电晕笼人工淋雨降雨率为12、16、20 mm/h条件下8×LGJ-630分裂导线电晕损失。并采用有效电晕损失等效计算方法,对电晕笼与试验线段试验结果进行等效计算分析。电晕笼与试验线段电晕损失基本等效,其误差在±6.5%范围内。研究结果验证了电晕笼分裂导线电晕损失试验结果与特高压交流同塔双回试验线段雨天监测结果的一致性,同时证明了有效电晕损失等效计算方法可以较为准确地将淋雨条件下电晕笼分裂导线电晕损失等效换算成特高压交流线路,研究成果可为特高压交流同塔双回输电线路电晕损失评估提供参考。
為瞭穫得特高壓交流同塔雙迴輸電線路雨天電暈損失評估的關鍵數據,採用特高壓交流同塔雙迴試驗線段、特高壓電暈籠兩種試驗手段,應用光纖數字化測量方法鑑測雨天氣象條件下特高壓交流同塔雙迴試驗線段電暈損失,測量特高壓電暈籠人工淋雨降雨率為12、16、20 mm/h條件下8×LGJ-630分裂導線電暈損失。併採用有效電暈損失等效計算方法,對電暈籠與試驗線段試驗結果進行等效計算分析。電暈籠與試驗線段電暈損失基本等效,其誤差在±6.5%範圍內。研究結果驗證瞭電暈籠分裂導線電暈損失試驗結果與特高壓交流同塔雙迴試驗線段雨天鑑測結果的一緻性,同時證明瞭有效電暈損失等效計算方法可以較為準確地將淋雨條件下電暈籠分裂導線電暈損失等效換算成特高壓交流線路,研究成果可為特高壓交流同塔雙迴輸電線路電暈損失評估提供參攷。
위료획득특고압교류동탑쌍회수전선로우천전훈손실평고적관건수거,채용특고압교류동탑쌍회시험선단、특고압전훈롱량충시험수단,응용광섬수자화측량방법감측우천기상조건하특고압교류동탑쌍회시험선단전훈손실,측량특고압전훈롱인공림우강우솔위12、16、20 mm/h조건하8×LGJ-630분렬도선전훈손실。병채용유효전훈손실등효계산방법,대전훈롱여시험선단시험결과진행등효계산분석。전훈롱여시험선단전훈손실기본등효,기오차재±6.5%범위내。연구결과험증료전훈롱분렬도선전훈손실시험결과여특고압교류동탑쌍회시험선단우천감측결과적일치성,동시증명료유효전훈손실등효계산방법가이교위준학지장림우조건하전훈롱분렬도선전훈손실등효환산성특고압교류선로,연구성과가위특고압교류동탑쌍회수전선로전훈손실평고제공삼고。
In order to obtain key data of corona loss of UHV AC double circuits transmission line under rain,two methods,namely,double circuits test line and UHV corona cage,were adopted,moreover,the optical fiber data measurement method was applied to monitor rainy corona loss of UHV AC double circuits test line in UHV corona cage,and 8×LGJ-630 bundle conductors' corona loss was measured under artificial rainfall rates of 12mm/h,16mm/h,and 20mm/h.Then the reduced corona loss equivalent calculation method was used based on the test results of corona cage and test line.The corona loss results of corona cage and test line were basically equivalent,and corona loss equivalent error was controlled in ±6.5% range.The research results verify that,the test results of bundle conductors' corona loss in corona cage are consistent with monitoring rainy corona loss of UHV AC double circuits test line,and the reduced corona loss equivalent calculation method is an effective way to convert bundle conductors' rainy corona loss in corona cage into the one of UHV AC line.The research results can provide a reference for UHV AC double circuits transmission line's corona loss evaluation.