张志劲%蒋兴良%孙才新%胡建林%张永记
張誌勁%蔣興良%孫纔新%鬍建林%張永記
장지경%장흥량%손재신%호건림%장영기
高海拔%现场试验%人工气候室%绝缘子%污闪%特性
高海拔%現場試驗%人工氣候室%絕緣子%汙閃%特性
고해발%현장시험%인공기후실%절연자%오섬%특성
high altitude%field test%artificial climate chamber%insulator%pollution flashover
高海拔下污秽绝缘子串电气性能将降低,国内外在高海拔现场和人工气候室对高海拔地区污秽绝缘子闪络特性开展了大量研究,但人工模拟试验结果与自然环境的试验结果等价性的问题罕见报道,分别在不同海拔的高海拔现场和人工气候室开展了不同型式绝缘子交流污闪特性对比试验研究,试验结果表明:蒸汽雾法下绝缘子交流污闪电压比湿污法下的高;随着海拔的增加,绝缘子串交流污闪电压将降低,其气压影响特征指数与绝缘子型式、盐密等有关;人工模拟试验结果与自然环境的试验结果具有等价性关系的研究结果可为高海拔地区输电线路外绝缘的选择和设计提供参考。
高海拔下汙穢絕緣子串電氣性能將降低,國內外在高海拔現場和人工氣候室對高海拔地區汙穢絕緣子閃絡特性開展瞭大量研究,但人工模擬試驗結果與自然環境的試驗結果等價性的問題罕見報道,分彆在不同海拔的高海拔現場和人工氣候室開展瞭不同型式絕緣子交流汙閃特性對比試驗研究,試驗結果錶明:蒸汽霧法下絕緣子交流汙閃電壓比濕汙法下的高;隨著海拔的增加,絕緣子串交流汙閃電壓將降低,其氣壓影響特徵指數與絕緣子型式、鹽密等有關;人工模擬試驗結果與自然環境的試驗結果具有等價性關繫的研究結果可為高海拔地區輸電線路外絕緣的選擇和設計提供參攷。
고해발하오예절연자천전기성능장강저,국내외재고해발현장화인공기후실대고해발지구오예절연자섬락특성개전료대량연구,단인공모의시험결과여자연배경적시험결과등개성적문제한견보도,분별재불동해발적고해발현장화인공기후실개전료불동형식절연자교류오섬특성대비시험연구,시험결과표명:증기무법하절연자교류오섬전압비습오법하적고;수착해발적증가,절연자천교류오섬전압장강저,기기압영향특정지수여절연자형식、염밀등유관;인공모의시험결과여자연배경적시험결과구유등개성관계적연구결과가위고해발지구수전선로외절연적선택화설계제공삼고。
Electric performance of polluted insulator string deteriorates in high altitude regions. Lots of researches on flashover performance of polluted insulators under high altitude conditions are performed in high altitude sites and in artificial climate chambers home and abroad, however, the research results related to the equivalence between the test results performed in natural environment and those under artificial simulation are rarely reported. For this reason, the comparative testing researches on AC pollution flashover performances of various types of insulators in the sites with different high altitudes as well as those in artificial climate chamber are carried out respectively. Testing results show that the AC pollution flashover voltage under the condition of steam fog method is higher than that under the condition of slurry method; the AC pollution flashover voltage of insulator string decreases with the increasing of altitude and the exponent describing the influence degree of air pressure on pollution flashover voltage is related to the types of insulators and salt density and so on. Results of this research show that there is equivalence between the testing results in natural environment and those of artificial simulation, and this conclusion is available for reference to both selection and design of external insulation for transmission lines located at high altitude regions.