那虎%李亚梅%魏志勇%李伟昭%姚莉%姚斯立
那虎%李亞梅%魏誌勇%李偉昭%姚莉%姚斯立
나호%리아매%위지용%리위소%요리%요사립
失步故障%1%100%kV断路器%分闸电阻%主辅断口%瞬态恢复电压%数学模型%PSCAD程序仿真
失步故障%1%100%kV斷路器%分閘電阻%主輔斷口%瞬態恢複電壓%數學模型%PSCAD程序倣真
실보고장%1%100%kV단로기%분갑전조%주보단구%순태회복전압%수학모형%PSCAD정서방진
out-of-phase fault%1 100 kV circuit breaker%opening resistance%primary and auxiliary breaker%transient recovery voltage%math model%PSCAD program simulation
对带分闸电阻的1100kV断路器的失步故障开断的过程进行研究。由于分闸电阻的存在,在开断过程中不可避免的改变了回路的特性参数,使得主辅断口承受了不同的瞬态恢复电压(TRV),通过等效模拟电路建立数学模型进行分析计算及PSCAD程序仿真,并同实际电网参数的模拟计算进行比较,结果表明:如果电网的实际参数较标准参数而言,在失步电流较小、上升率较低的情况下,对于带分闸电阻的断路器,在开断失步故障的条件下,辅助断口所要承受的TRV参数甚至可能比无分闸电阻断路器所承受的TRV还要苛刻,故需根据电网特性来选择是否使用带分闸电阻的断路器。
對帶分閘電阻的1100kV斷路器的失步故障開斷的過程進行研究。由于分閘電阻的存在,在開斷過程中不可避免的改變瞭迴路的特性參數,使得主輔斷口承受瞭不同的瞬態恢複電壓(TRV),通過等效模擬電路建立數學模型進行分析計算及PSCAD程序倣真,併同實際電網參數的模擬計算進行比較,結果錶明:如果電網的實際參數較標準參數而言,在失步電流較小、上升率較低的情況下,對于帶分閘電阻的斷路器,在開斷失步故障的條件下,輔助斷口所要承受的TRV參數甚至可能比無分閘電阻斷路器所承受的TRV還要苛刻,故需根據電網特性來選擇是否使用帶分閘電阻的斷路器。
대대분갑전조적1100kV단로기적실보고장개단적과정진행연구。유우분갑전조적존재,재개단과정중불가피면적개변료회로적특성삼수,사득주보단구승수료불동적순태회복전압(TRV),통과등효모의전로건립수학모형진행분석계산급PSCAD정서방진,병동실제전망삼수적모의계산진행비교,결과표명:여과전망적실제삼수교표준삼수이언,재실보전류교소、상승솔교저적정황하,대우대분갑전조적단로기,재개단실보고장적조건하,보조단구소요승수적TRV삼수심지가능비무분갑전조단로기소승수적TRV환요가각,고수근거전망특성래선택시부사용대분갑전조적단로기。
Study was carried out for process of out-of-phase fault of 1 100 kV circuit breaker's break-off with opening resistance. Due to the existing of opening resistance, in break-off process the characteristics parameters of feedback circuit were unavoidably changed, so as to make primary and auxiliary fractures to bear different transient recovery voltage (TRV). The math model was built via the equal effect analog circuit. This paper analyzed PSCAD program simulation and calculated the parameters of the model, comparing with analog calculation of actual grid parameters. The result shows that so far as actual parameters of grid compared with standard parameters, under the conditions of break-off out-of-phase fault with smaller out-of-phase current, lower rising rate, as for circuit breakers with opening resistance, the auxiliary fracture born TRV parameters would be even more strict than circuit breakers without opening resistance, therefore there is a need to select circuit breakers with opening resistance according to grid characteristics.