电网技术
電網技術
전망기술
POWER SYSTEM TECHNOLOGY
2012年
2期
206-211
,共6页
光纤复合架空地线%异常发热%感应电流%发热功率%现场测量%电磁仿真
光纖複閤架空地線%異常髮熱%感應電流%髮熱功率%現場測量%電磁倣真
광섬복합가공지선%이상발열%감응전류%발열공솔%현장측량%전자방진
optical fiber composite overhead ground wire (OPGW)%abnormal heating%induced current%heating power%on-site measurement%electromagnetic simulation
针对光纤复合架空地线foptical fiber composite overhead ground wire,OPGW)在变电站构架连接处的异常发热问题,对其接地回路感应电流、电压进行现场实测,分析出异常发热原因是构架处OPGW主接地不良导致接地电流转移至耐张连接回路,且发热功率较大及较集中。据此进一步开展OPGW感应电流、发热功率的仿真研究,仿真与实测数据基本吻合。研究表明线路负荷电流、杆塔接地电阻以及OPGW与构架连接接触电阻对OPGW接地回路分流及发热功率存在不同程度的影响。
針對光纖複閤架空地線foptical fiber composite overhead ground wire,OPGW)在變電站構架連接處的異常髮熱問題,對其接地迴路感應電流、電壓進行現場實測,分析齣異常髮熱原因是構架處OPGW主接地不良導緻接地電流轉移至耐張連接迴路,且髮熱功率較大及較集中。據此進一步開展OPGW感應電流、髮熱功率的倣真研究,倣真與實測數據基本吻閤。研究錶明線路負荷電流、桿塔接地電阻以及OPGW與構架連接接觸電阻對OPGW接地迴路分流及髮熱功率存在不同程度的影響。
침대광섬복합가공지선foptical fiber composite overhead ground wire,OPGW)재변전참구가련접처적이상발열문제,대기접지회로감응전류、전압진행현장실측,분석출이상발열원인시구가처OPGW주접지불량도치접지전류전이지내장련접회로,차발열공솔교대급교집중。거차진일보개전OPGW감응전류、발열공솔적방진연구,방진여실측수거기본문합。연구표명선로부하전류、간탑접지전조이급OPGW여구가련접접촉전조대OPGW접지회로분류급발열공솔존재불동정도적영향。
In allusion to the phenomenon of abnormal heating at the joint where the optical fiber composite overhead ground wire (OPGW) is connected to the truss of substation, the on-site measurement of the induced current and voltage of the grounding circuit of OPGW was performed, and based on the measured results the reason causing the abnormal heating was analyzed. Analysis results showed that the bad contact of OPGW with the truss made the grounding current of OPGW transferring to the circuit of tensional joint and the heating power was larger and concentrated. On this basis the simulation research on induced current of OPGW and heating power are conducted, and simulation results basically conform to the measured data. Research results show that power flow of transmission line, tower grounding resistance and contact resistance of the joint where OPGW is connected to the truss differently influence on the shunt of grounding current of OPGW and the heating power.