土木建筑与环境工程
土木建築與環境工程
토목건축여배경공정
JOURNAL OF CIVIL, ARCHITECTURAL & ENVIRONMENTAL ENGINEERING
2009年
5期
1-8
,共8页
曹现雷%郝际平%曹志民%张天光%张耀%李天际
曹現雷%郝際平%曹誌民%張天光%張耀%李天際
조현뢰%학제평%조지민%장천광%장요%리천제
屈曲%角钢%试验研究%有限单元法%支座
屈麯%角鋼%試驗研究%有限單元法%支座
굴곡%각강%시험연구%유한단원법%지좌
buckling%angles%experimental study%finite element method(FEM)%bearing
为了研究输电塔中Q460高强角钢一端偏心压杆受力性能,通过试验与理论计算方法分析了受压试件的整体稳定和局部屈曲情况,试件轴心端采用球铰和双刀口支座模拟,考察了不同端部条件和残余应力等对角钢受力性能的影响,结果表明:试件轴心端无论采用球铰支座或双刀口支座形式,均能较准确反映角钢构件的受力性能,残余应力对试件承载力影响小于5%.比较了试验、有限元法、美国<输电铁塔设计导则>(ASCE 10-1997)和中国<架空送电线路杆塔结构设计技术规定>(DL/T 5154-2002)对角钢极限承载力值的不同处理方法,指出采用DL/T 5154-2002标准计算方法对高强钢杆件承载力得出的结果偏保守,在此基础上,提出了对实际材料强度除以抗力分项系数rR=1.111后改造的ASCE设计方法.
為瞭研究輸電塔中Q460高彊角鋼一耑偏心壓桿受力性能,通過試驗與理論計算方法分析瞭受壓試件的整體穩定和跼部屈麯情況,試件軸心耑採用毬鉸和雙刀口支座模擬,攷察瞭不同耑部條件和殘餘應力等對角鋼受力性能的影響,結果錶明:試件軸心耑無論採用毬鉸支座或雙刀口支座形式,均能較準確反映角鋼構件的受力性能,殘餘應力對試件承載力影響小于5%.比較瞭試驗、有限元法、美國<輸電鐵塔設計導則>(ASCE 10-1997)和中國<架空送電線路桿塔結構設計技術規定>(DL/T 5154-2002)對角鋼極限承載力值的不同處理方法,指齣採用DL/T 5154-2002標準計算方法對高彊鋼桿件承載力得齣的結果偏保守,在此基礎上,提齣瞭對實際材料彊度除以抗力分項繫數rR=1.111後改造的ASCE設計方法.
위료연구수전탑중Q460고강각강일단편심압간수력성능,통과시험여이론계산방법분석료수압시건적정체은정화국부굴곡정황,시건축심단채용구교화쌍도구지좌모의,고찰료불동단부조건화잔여응력등대각강수력성능적영향,결과표명:시건축심단무론채용구교지좌혹쌍도구지좌형식,균능교준학반영각강구건적수력성능,잔여응력대시건승재력영향소우5%.비교료시험、유한원법、미국<수전철탑설계도칙>(ASCE 10-1997)화중국<가공송전선로간탑결구설계기술규정>(DL/T 5154-2002)대각강겁한승재력치적불동처리방법,지출채용DL/T 5154-2002표준계산방법대고강강간건승재력득출적결과편보수,재차기출상,제출료대실제재료강도제이항력분항계수rR=1.111후개조적ASCE설계방법.
To analyze mechanical behavior of Q460 high-strength single-angle steel struts with an eccentric load at one end in transmission towers, experimental analysis and theoretical calculation were carried out to study the overall stability and local buckling of members. Spherical hinge bearing and double knife-edge bearing were applied at axial end of specimens. Influence of some factors on bearing capacity of compression
members with eccentricities at both ends was analyzed, such as the end supporting conditions and residual stresses. It was shown that whether spherical hinge bearing or double knife-edge bearing was used at axial end, the mechanical behavior can be accurately presented and the residual stresses affected the ultimate load-carrying capacity by about 5 ~ or less. Compared with different methods, such as experiment method, finite element method, method in the Guide for American Design of Latticed Steel Transmission Structure (ASCE10-1997)and method in Chinese Technical Regulation of Design for Tower and Pole Structure of Overhead Transmission Line (DL/TS154-2002), it was found that the calculated strength of high strength steel member by standard calculation method in DL/T5154- 2000 was over-conservative.According to the research results, the revised formulas of ASCE were proposed with dividing actual
material strength by the resistance coefficient of rR=1. 111. Therefore, the experimental results can provide
reference for designing high-strength Q460 single-angle steel members compressed eccentrically at one end.