Engineering thermophysics%Air source heat pump%Frost growth characteristics%Dynamic performance%Frosting experiment
在室外环境空气温度-15℃~5℃、相对湿度65%~90%范围内,对一台空气源热泵室外换热器表面霜层生长特性及热泵系统动态性能进行了实验研究.实验结果表明,翅片表面霜层厚度呈分段增长模式,在结霜初始段,霜层主要由粒状冰晶组成,并逐渐形成柱状冰晶,其厚度增长较快;在第二阶段为柱状冰晶主要在其半径方向生长,霜层厚度增长速度减慢;而在第三阶段,柱状冰晶主要在其高度方向生长,逐渐形成针状冰晶,霜层厚度增长速度迅速增大至第二阶段的3~5.8倍.对实验结果的分析表明,热泵机组性能恶化主要是由于蒸发器表面温度下降、霜晶形态变化引起霜层厚度快速增长及空气流动阻力增加导致风机流量下降三个因素之间形成的恶性循环所致,其中换热器表面温度下降引起的霜晶形态变化起到了至关重要的作用.
在室外環境空氣溫度-15℃~5℃、相對濕度65%~90%範圍內,對一檯空氣源熱泵室外換熱器錶麵霜層生長特性及熱泵繫統動態性能進行瞭實驗研究.實驗結果錶明,翅片錶麵霜層厚度呈分段增長模式,在結霜初始段,霜層主要由粒狀冰晶組成,併逐漸形成柱狀冰晶,其厚度增長較快;在第二階段為柱狀冰晶主要在其半徑方嚮生長,霜層厚度增長速度減慢;而在第三階段,柱狀冰晶主要在其高度方嚮生長,逐漸形成針狀冰晶,霜層厚度增長速度迅速增大至第二階段的3~5.8倍.對實驗結果的分析錶明,熱泵機組性能噁化主要是由于蒸髮器錶麵溫度下降、霜晶形態變化引起霜層厚度快速增長及空氣流動阻力增加導緻風機流量下降三箇因素之間形成的噁性循環所緻,其中換熱器錶麵溫度下降引起的霜晶形態變化起到瞭至關重要的作用.
재실외배경공기온도-15℃~5℃、상대습도65%~90%범위내,대일태공기원열빙실외환열기표면상층생장특성급열빙계통동태성능진행료실험연구.실험결과표명,시편표면상층후도정분단증장모식,재결상초시단,상층주요유립상빙정조성,병축점형성주상빙정,기후도증장교쾌;재제이계단위주상빙정주요재기반경방향생장,상층후도증장속도감만;이재제삼계단,주상빙정주요재기고도방향생장,축점형성침상빙정,상층후도증장속도신속증대지제이계단적3~5.8배.대실험결과적분석표명,열빙궤조성능악화주요시유우증발기표면온도하강、상정형태변화인기상층후도쾌속증장급공기류동조력증가도치풍궤류량하강삼개인소지간형성적악성순배소치,기중환열기표면온도하강인기적상정형태변화기도료지관중요적작용.
The frost growth characteristics on the outdoor heat exchanger and the dynamic performance of an air source heat pump(ASHP)were experimentally investigated.The experimental outdoor air temperature ranged from-15 to 5℃,and relative humidity was from 65% to 90%.The results indicate that the frost grew in three stages.In the initial stage,the granular ices grew on the surface,and then the column-shaped ice crystals were formed gradually and the frost thickness rose quickly.After the first stage,the column-shaped ice crystals grew in its radius rather than in its length,and thus the growth rate of frost thickness decreased with the frosting time.In the third stage,the column-shaped ice crystals grew mainly in its length and the ice crystals had the acerose shape gradually,and the growth rate of frost thickness increased rapidly to 3-5.8 times that in the second stage.It is found that the performance degradation of the ASHP unit was caused by the wall temperature drop of the evaporator,the rapid increase in the frost thickness,and the decrease in the air flow rate.