电力系统自动化
電力繫統自動化
전력계통자동화
AUTOMATION OF ELECTRIC POWER SYSTEMS
2011年
19期
77-84
,共8页
谢惠藩%王海军%陈潜
謝惠藩%王海軍%陳潛
사혜번%왕해군%진잠
直流融冰功能%电磁暂态仿真%双极功率异向传输%无功功率%谐波分析%特征谐波%非特征谐波
直流融冰功能%電磁暫態倣真%雙極功率異嚮傳輸%無功功率%諧波分析%特徵諧波%非特徵諧波
직류융빙공능%전자잠태방진%쌍겁공솔이향전수%무공공솔%해파분석%특정해파%비특정해파
direct current power deicing function%EMTDC%direct current power forth-and-reverse transmission%reactivepower%harmonic analysis%characteristic harmonic%non-characteristic harmonic
为研究高肇(高坡一肇庆)直流融冰模式、正常模式的无功特性和谐波特性,基于EMTDC搭建了±500kV高肇直流背靠背融冰详细模型并重点针对融冰模式、正常模式下换流站的无功特性和交直流侧谐波特性进行仿真研究。仿真结果表明:高坡站融冰模式的无功消耗比正常模式略大,肇庆站融冰模式的无功消耗则比正常模式略小;融冰模式下换流站交流谐波电流幅值比正常模式小、畸变率比正常模式大,而交流谐波电压及其畸变率均比正常模式小;融冰模式下同一换流站中两极处于不同的运行状态,两极直流侧谐波特性不相同。该研究结果为高肇直流在融冰方式下滤波器的投切提供一定的理论指导。
為研究高肇(高坡一肇慶)直流融冰模式、正常模式的無功特性和諧波特性,基于EMTDC搭建瞭±500kV高肇直流揹靠揹融冰詳細模型併重點針對融冰模式、正常模式下換流站的無功特性和交直流側諧波特性進行倣真研究。倣真結果錶明:高坡站融冰模式的無功消耗比正常模式略大,肇慶站融冰模式的無功消耗則比正常模式略小;融冰模式下換流站交流諧波電流幅值比正常模式小、畸變率比正常模式大,而交流諧波電壓及其畸變率均比正常模式小;融冰模式下同一換流站中兩極處于不同的運行狀態,兩極直流側諧波特性不相同。該研究結果為高肇直流在融冰方式下濾波器的投切提供一定的理論指導。
위연구고조(고파일조경)직류융빙모식、정상모식적무공특성화해파특성,기우EMTDC탑건료±500kV고조직류배고배융빙상세모형병중점침대융빙모식、정상모식하환류참적무공특성화교직류측해파특성진행방진연구。방진결과표명:고파참융빙모식적무공소모비정상모식략대,조경참융빙모식적무공소모칙비정상모식략소;융빙모식하환류참교류해파전류폭치비정상모식소、기변솔비정상모식대,이교류해파전압급기기변솔균비정상모식소;융빙모식하동일환류참중량겁처우불동적운행상태,량겁직류측해파특성불상동。해연구결과위고조직류재융빙방식하려파기적투절제공일정적이론지도。
To study the characteristics of reactive power and harmonic of Gao-Zhao high voltage direct current (HV[)C) under deicing operation mode and normal operation mode, an EMTDC model of ~500 kV C-ao-Zhao HVDC with direct current power forth-and reverse transmission deicing function is introduced in detail. With this model the characteristics of reactive power and harmonic at converter station are analyzed. Simulations show that: (1) Reactive power consumption at Gaopo converter station under deicing operation mode is larger than that under normal operation mode, while Zhaoqing converter station is on the contrary; (2) The amplitude of harmonic alternative current is smaller and total harmonic current distortion rate is larger compared to the normal operation mode, and the amplitude and harmonic distortion rate of alternative current voltage are both smaller than that of normal operation mode; (3) The two poles operating at different modes and the harmonic in direct system of each pole in the same converter station is different. Simulation results are helpful to the control of alternative current filter control under deicing operation mode.