capillary tube%radiant heating%operating cost%heat source scheme%technical and economic analysis
首先介绍毛细管辐射采暖地面和顶棚构造,并采用试验方法分析热泵机组供热性能,然后采用BIN法计算不同热源方案毛细管采暖系统能耗,分析其节能性;最后分析各热源方案的初投资和运行费用以及其对环境影响.通过研究得出:(1)地源热泵机组提供28~35℃的低温热水时的COP值与制取40~50℃热水相比大大提高,节能效果显著;(2)在冬季采暖总耗煤量方面,地源热泵系统最小,与风冷热泵、天然气燃气炉相比分别节省了32.9%、129%的耗煤量;(3)采用天燃气采暖炉为热源时,污染物排放量最少,对环境破坏最小;(4)从经济方面分析,风冷热泵冷热水机组是最优的热源方案.
首先介紹毛細管輻射採暖地麵和頂棚構造,併採用試驗方法分析熱泵機組供熱性能,然後採用BIN法計算不同熱源方案毛細管採暖繫統能耗,分析其節能性;最後分析各熱源方案的初投資和運行費用以及其對環境影響.通過研究得齣:(1)地源熱泵機組提供28~35℃的低溫熱水時的COP值與製取40~50℃熱水相比大大提高,節能效果顯著;(2)在鼕季採暖總耗煤量方麵,地源熱泵繫統最小,與風冷熱泵、天然氣燃氣爐相比分彆節省瞭32.9%、129%的耗煤量;(3)採用天燃氣採暖爐為熱源時,汙染物排放量最少,對環境破壞最小;(4)從經濟方麵分析,風冷熱泵冷熱水機組是最優的熱源方案.
수선개소모세관복사채난지면화정붕구조,병채용시험방법분석열빙궤조공열성능,연후채용BIN법계산불동열원방안모세관채난계통능모,분석기절능성;최후분석각열원방안적초투자화운행비용이급기대배경영향.통과연구득출:(1)지원열빙궤조제공28~35℃적저온열수시적COP치여제취40~50℃열수상비대대제고,절능효과현저;(2)재동계채난총모매량방면,지원열빙계통최소,여풍랭열빙、천연기연기로상비분별절성료32.9%、129%적모매량;(3)채용천연기채난로위열원시,오염물배방량최소,대배경파배최소;(4)종경제방면분석,풍랭열빙랭열수궤조시최우적열원방안.
The article presented particularly the arrangement form and structure of ceiling and floor of capillary tube mat. The experimental method was employed to study heating performance of heat hump unit. And then, BIN method was adopted to calculate heating energy consumption of radiant heating system of capillary tube with different heat source schemes and analyse its energy efficiency. At same the time, its investment, operating cost, and environmental impact was analysed. Through the analysis, some conclusions could be drawn as follows:(1)coefficient of performance COP of heat pump unit in heating mode was greatly improved when the average supply water temperature was 28~35℃ compared with 40~50℃. So the effect of energy conservation was apparent.(2)when the ground source heat pump compared with air cooled heat pump and the gas furnace with natural gas, its heating coal consumption had saved more 32.9%, 129% respectively.(3)discharging pollutant of gas furnace with natural gas were less than that of other schemes , so it was most environmental friendly in all schemes.(4) on the economy, air cooled heat pump was the best heat source scheme in all schemes.