清华大学学报(英文版)
清華大學學報(英文版)
청화대학학보(영문판)
TSINGHUA SCIENCE AND TECHNOLOGY
2001年
5期
500-502
,共3页
王黎明%关志成%胡祺昊%梁曦东%盛新富%N.L.Allen
王黎明%關誌成%鬍祺昊%樑晞東%盛新富%N.L.Allen
왕려명%관지성%호기호%량희동%성신부%N.L.Allen
sparkover%composite voltage%conductor-rod gap
More and more high voltage transmission lines make use of rubber housed ZnO arresters in series with another air gap (for example, the insulator gap) as lighting protection elements. Many test results of ZnO arresters protection performance show that this insulation arrangement is suitable for practical lines according to results based on only simple impulse voltage. This paper uses a composite voltage (switching impulse voltage/alternating voltage) to determine the air breakdown behavior of the conductor-rod gap in series with the sphere gap. In the test, the switching impulse voltage is applied to the conductor while the alternating voltage is applied to the rod and one sphere and the other sphere is grounded. The results show that in some cases, the value of the U50% sparkover voltage for the conductor-rod gap with the composite voltage is nearly only half of that for just the simple impulse voltage.