袁江涛%杨立%王小川%张健%金仁喜
袁江濤%楊立%王小川%張健%金仁喜
원강도%양립%왕소천%장건%금인희
图像处理%雾滴尺寸%机器视觉%图像采集
圖像處理%霧滴呎吋%機器視覺%圖像採集
도상처리%무적척촌%궤기시각%도상채집
image processing%droplet size%machine vision%image collecting
为了满足科研与工程中对细水雾液滴尺寸测量的高精度低成本要求,对雾滴尺寸的机器视觉测量方法进行了深入研究.在自行建立的高压喷雾系统与雾滴采集装置上对细水雾液滴进行了采样,用显微镜及其CCD相机对雾滴样本进行了图像采集,用图像处理软件对采集的雾滴图像进行了处理与分析,测量并统计了5966个雾滴,得到了雾滴尺寸的频谱分布和累积分布以及雾滴平均直径和特征直径,将测量结果与相位多普勒粒子分析仪(PDPA)的测量结果进行了比较.结果表明,机器视觉方法町测量的最小雾滴直径约4.39 μm;机器视觉测量结果与PDPA测最结果相当接近,两种方法测得的细水雾液滴平均直径和特征直径的相对误差均在5%以内,雾滴尺寸均匀度指数的相对误差为0.27%.
為瞭滿足科研與工程中對細水霧液滴呎吋測量的高精度低成本要求,對霧滴呎吋的機器視覺測量方法進行瞭深入研究.在自行建立的高壓噴霧繫統與霧滴採集裝置上對細水霧液滴進行瞭採樣,用顯微鏡及其CCD相機對霧滴樣本進行瞭圖像採集,用圖像處理軟件對採集的霧滴圖像進行瞭處理與分析,測量併統計瞭5966箇霧滴,得到瞭霧滴呎吋的頻譜分佈和纍積分佈以及霧滴平均直徑和特徵直徑,將測量結果與相位多普勒粒子分析儀(PDPA)的測量結果進行瞭比較.結果錶明,機器視覺方法町測量的最小霧滴直徑約4.39 μm;機器視覺測量結果與PDPA測最結果相噹接近,兩種方法測得的細水霧液滴平均直徑和特徵直徑的相對誤差均在5%以內,霧滴呎吋均勻度指數的相對誤差為0.27%.
위료만족과연여공정중대세수무액적척촌측량적고정도저성본요구,대무적척촌적궤기시각측량방법진행료심입연구.재자행건립적고압분무계통여무적채집장치상대세수무액적진행료채양,용현미경급기CCD상궤대무적양본진행료도상채집,용도상처리연건대채집적무적도상진행료처리여분석,측량병통계료5966개무적,득도료무적척촌적빈보분포화루적분포이급무적평균직경화특정직경,장측량결과여상위다보륵입자분석의(PDPA)적측량결과진행료비교.결과표명,궤기시각방법정측량적최소무적직경약4.39 μm;궤기시각측량결과여PDPA측최결과상당접근,량충방법측득적세수무액적평균직경화특정직경적상대오차균재5%이내,무적척촌균균도지수적상대오차위0.27%.
In order to meeting the demand of measuring the water mist droplet size with high accuracy and low cost, the machine vision measuring technique for the droplet size was studied in depth. The water mist droplets were sampled in self-building high pressure spraying system and droplets collecting device, the photos of the droplets sample were taken by the microscope and its CCD camera, the droplets sample photos were processed and analysed using the image processing software. The total number of the measured and counted droplets was 5966. The droplet size spectral, cumulative distribution and the droplet mean and indicated diameter were obtained. The machine vision measuring results were compared with the PDPA measuring results. Results indicate that the minimum droplet which the machine vision technique can be used to measure is 4.39 μm, and the machine vision results are close to the PDPA measuring results. The relative errors of the water mist droplet mean and indicated diameter are less than 5%, and that of the droplet size dispersion coefficient is 0.27%.