为检测电容器内部元件的损坏故障,高压直流输电(high voltage DC transmission,HVDC)I程中交直流滤波器的高压电容器通常采用H形接线或分支接线形式,进而配置电容器不平衡保护作为反映该类故障的主保护。然而一些HVDC工程中电容器不平衡保护仍存在隐患。为此分别针对上述2种接线形式的电容器,定量推导了单个支路电容器的故障发展过程中及2个支路电容器均有电容元件击穿时的不平衡电流及相应过电压倍数。分别对2种接线的电容器不平衡保护提出了实用的判据,并探讨了相应的整定计算原则及动作策略。
為檢測電容器內部元件的損壞故障,高壓直流輸電(high voltage DC transmission,HVDC)I程中交直流濾波器的高壓電容器通常採用H形接線或分支接線形式,進而配置電容器不平衡保護作為反映該類故障的主保護。然而一些HVDC工程中電容器不平衡保護仍存在隱患。為此分彆針對上述2種接線形式的電容器,定量推導瞭單箇支路電容器的故障髮展過程中及2箇支路電容器均有電容元件擊穿時的不平衡電流及相應過電壓倍數。分彆對2種接線的電容器不平衡保護提齣瞭實用的判據,併探討瞭相應的整定計算原則及動作策略。
위검측전용기내부원건적손배고장,고압직류수전(high voltage DC transmission,HVDC)I정중교직류려파기적고압전용기통상채용H형접선혹분지접선형식,진이배치전용기불평형보호작위반영해류고장적주보호。연이일사HVDC공정중전용기불평형보호잉존재은환。위차분별침대상술2충접선형식적전용기,정량추도료단개지로전용기적고장발전과정중급2개지로전용기균유전용원건격천시적불평형전류급상응과전압배수。분별대2충접선적전용기불평형보호제출료실용적판거,병탐토료상응적정정계산원칙급동작책략。
To detect the failure of a component inside capacitors, the H-shaped or branch wirings are generally adopted for high voltage capacitors in AC/DC filters of HVDC transmission projects, and then as the main protection of this kind of faults the unbalance protection for capacitors are equipped. However, there are hidden troubles in the unbalance protection for capacitors of HVDC transmission projects. For this reason, for above-mentioned two wiring forms the unbalanced current during fault progression of single branch capacitor and the unbalanced current while the breakdown of capacitor components in both branches occurred as well as corresponding overvoltage multiples under the two conditions are quantitatively derived. On this basis practicable criteria of unbalance protection for capacitors using above-mentioned two wiring forms are proposed, and corresponding principle of setting calculation and action strategy for different failure conditions are discussed.