reverse osmosis system%humic acid%calcium ions%membrane fouling
通过单一污染物试验,分析了腐殖酸对长流程反渗透系统的污染过程,指出了腐殖酸污染会导致系统工作压力上升,透盐率下降及前后段通量失衡的现象.复合污染试验表明,钙离子与腐殖酸的络合效应使系统达到固定污染效果所需的运行时间大大缩短,且系统透盐率高于单一污染.
通過單一汙染物試驗,分析瞭腐殖痠對長流程反滲透繫統的汙染過程,指齣瞭腐殖痠汙染會導緻繫統工作壓力上升,透鹽率下降及前後段通量失衡的現象.複閤汙染試驗錶明,鈣離子與腐殖痠的絡閤效應使繫統達到固定汙染效果所需的運行時間大大縮短,且繫統透鹽率高于單一汙染.
통과단일오염물시험,분석료부식산대장류정반삼투계통적오염과정,지출료부식산오염회도치계통공작압력상승,투염솔하강급전후단통량실형적현상.복합오염시험표명,개리자여부식산적락합효응사계통체도고정오염효과소수적운행시간대대축단,차계통투염솔고우단일오염.
By single fouling experiments, fouling processes of long flow RO system by HA were analyzed, and it was pointed out that fouling by HA would cause the increase of system work pressure, the decrease of system salt permeability, and the aggravation of system flux imbalance. The compound fouling experiments showed that due to complexing effect caused by Ca2+ and HA, the system fouling time was greatly shortened and the system salt permeability was higher than single fouling.