分析了火力发电厂因启动大容量高压电动机及380 V母线切换时的母线电压波动,造成空冷机组空冷岛冷却风机变频器跳闸停运的原因,并提出了改进措施。通过优化热控逻辑、变频器设置及控制回路改造,使变频器在母线电压恢复后能成功自启动,以提高空冷变频装置的可靠性,减少对汽轮机背压的扰动。
分析瞭火力髮電廠因啟動大容量高壓電動機及380 V母線切換時的母線電壓波動,造成空冷機組空冷島冷卻風機變頻器跳閘停運的原因,併提齣瞭改進措施。通過優化熱控邏輯、變頻器設置及控製迴路改造,使變頻器在母線電壓恢複後能成功自啟動,以提高空冷變頻裝置的可靠性,減少對汽輪機揹壓的擾動。
분석료화력발전엄인계동대용량고압전동궤급380 V모선절환시적모선전압파동,조성공랭궤조공랭도냉각풍궤변빈기도갑정운적원인,병제출료개진조시。통과우화열공라집、변빈기설치급공제회로개조,사변빈기재모선전압회복후능성공자계동,이제고공랭변빈장치적가고성,감소대기륜궤배압적우동。
This paper analyzes the reasons of air-cooling island inverter tripping,which was caused by bus voltage fluctuations aroused by large-capacity high-voltage motors starting up and 380 V bus switchover,and improvements were put forward accordingly. By optimizing the thermal control logic,inverter setting and the control loop,the inverter can self-start successfully after the voltage recovers so that the reliability of air-cooling inverter can be improved and the disturbance to the turbine back pressure can be prevented.