中国舰船研究
中國艦船研究
중국함선연구
CHINESE JOURNAL OF SHIP RESEARCH
2014年
2期
89-94,116
,共7页
船舶中压电网%高阻接地%熄弧恢复电压%重燃过电压%故障电流
船舶中壓電網%高阻接地%熄弧恢複電壓%重燃過電壓%故障電流
선박중압전망%고조접지%식호회복전압%중연과전압%고장전류
shipboard medium voltage power grid%High Resistance Grounding(HRG)%arc-extinct re-covery voltage%re-strike overvoltage%fault current
高阻接地方式用于船舶中压电网时,对其机理和规律迄今还缺乏定量研究。在对船舶中压电网单相接地故障进行理论分析的基础上,以一个具有励磁电压控制及柴油机调速的单机系统为例,结合Simulink暂态仿真,研究阻抗比、发电机频率偏移、燃弧时刻角以及故障点过渡电阻等对熄弧恢复电压、重燃过电压、中性点位移电压以及故障电流的影响。结果表明:随阻抗比增加,熄弧电压恢复过渡时间越长,恢复电压峰值越大,重燃过电压也越严重;提高阻抗比可减小故障电流,但减小程度逐渐趋缓,还会使重燃过电压增加;发电机频率偏移可能会引起较大的暂态过电压;燃弧时刻对故障电流几乎没有影响。最后给出高阻接地方式的一般配置原则。
高阻接地方式用于船舶中壓電網時,對其機理和規律迄今還缺乏定量研究。在對船舶中壓電網單相接地故障進行理論分析的基礎上,以一箇具有勵磁電壓控製及柴油機調速的單機繫統為例,結閤Simulink暫態倣真,研究阻抗比、髮電機頻率偏移、燃弧時刻角以及故障點過渡電阻等對熄弧恢複電壓、重燃過電壓、中性點位移電壓以及故障電流的影響。結果錶明:隨阻抗比增加,熄弧電壓恢複過渡時間越長,恢複電壓峰值越大,重燃過電壓也越嚴重;提高阻抗比可減小故障電流,但減小程度逐漸趨緩,還會使重燃過電壓增加;髮電機頻率偏移可能會引起較大的暫態過電壓;燃弧時刻對故障電流幾乎沒有影響。最後給齣高阻接地方式的一般配置原則。
고조접지방식용우선박중압전망시,대기궤리화규률흘금환결핍정량연구。재대선박중압전망단상접지고장진행이론분석적기출상,이일개구유려자전압공제급시유궤조속적단궤계통위례,결합Simulink잠태방진,연구조항비、발전궤빈솔편이、연호시각각이급고장점과도전조등대식호회복전압、중연과전압、중성점위이전압이급고장전류적영향。결과표명:수조항비증가,식호전압회복과도시간월장,회복전압봉치월대,중연과전압야월엄중;제고조항비가감소고장전류,단감소정도축점추완,환회사중연과전압증가;발전궤빈솔편이가능회인기교대적잠태과전압;연호시각대고장전류궤호몰유영향。최후급출고조접지방식적일반배치원칙。
When High Resistance Grounding(HRG)is used for shipboard Medium Voltage(MV)power grid,the mechanisms and laws can be quite complicated,which so far lacks quantitative research. Based on the theoretical analysis of single-phase ground fault for shipboard MV power grid,and taking a stand-alone system with diesel engine and excitation voltage control as example,this paper studies the HRG in detail combined with Simulink transient simulation. The research mainly focuses on the impact of impedance ratio of HRG on arc-extinct recovery voltage,re-strike overvoltage,neutral displacement volt-age,and fault current. In addition,the effects of generator frequency offset,arc angle,and fault transition re-sistance are also discussed. The results show that with the increase of impedance ratio,the longer the time of arc-extinct recovery voltage is,and the higher the peak of arc-extinct recovery voltage,the more seri-ous the re-strike overvoltage is. Increasing the impedance ratio could decrease the fault current,but the degree will slow down gradually. The generator frequency offsets can lead to greater transient overvoltage, while the arcing time angle has little impact on the fault current. At last,the general principle of HRG con-figuration is given.