以西气东输三线某站场电驱站冷却水系统调试为例,介绍了该冷却水系统在调试时出现的流量与扬程紊乱且不呈反比关系的问题,通过对提前打压、止回阀、循环水泵、过滤器、电磁流量计和冷却水系统水力过程进行分析,找出问题的原因,并提出了相关解决措施和建议。
以西氣東輸三線某站場電驅站冷卻水繫統調試為例,介紹瞭該冷卻水繫統在調試時齣現的流量與颺程紊亂且不呈反比關繫的問題,通過對提前打壓、止迴閥、循環水泵、過濾器、電磁流量計和冷卻水繫統水力過程進行分析,找齣問題的原因,併提齣瞭相關解決措施和建議。
이서기동수삼선모참장전구참냉각수계통조시위례,개소료해냉각수계통재조시시출현적류량여양정문란차불정반비관계적문제,통과대제전타압、지회벌、순배수빙、과려기、전자류량계화냉각수계통수력과정진행분석,조출문제적원인,병제출료상관해결조시화건의。
Taking the cooling water system commissioning proj ect of a station of West to East Gas Pipeline as an example,this paper introduced the problems in the cooling water system commissioning,which meant that the disorder between the flow rate and water head and the rela-tionship between was not inverse proportion.Through the analysis of boosting in advance nonre-turn valve,recycling pump,filter,magnetic flow rate meter,and the hydraulic process of the cool-ing water system,the reasons for the problems were figured out and the corresponding measure and suggest were offered.