天津大学学报(英文版)
天津大學學報(英文版)
천진대학학보(영문판)
TRANSACTIONS OF TIANJIN UNIVERSITY
2014年
1期
42-47
,共6页
dry cooling%dedicated ventilation%building energy simulation%energy performance%condensation risk
The combined use of dry cooling (DC) system and dedicated ventilation (DV) system to decouple cool-ing and dehumidification process for energy efficiency was proposed for subtropical climates like Hong Kong. In this study, the energy performance and condensation risk of the use of DCDV system were examined by analyzing its ap-plication in a typical office building in Hong Kong. Through hour-by-hour simulation using actual equipment per-formance data and realistic building and system characteristics, it was found that with the use of DCDV system, the annual energy consumption could be reduced by 54%in comparison with the conventional system (constant air vol-ume with reheat system). In respect of condensation risk, it was found that the annual frequency of occurrence of con-densation on DC coil was 35 h. Additional simulations were conducted to examine the influence of different parame-ters on the condensation risk of DCDV system. Measures to ensure condensate-free on DC coil were also discussed.