广东电力
廣東電力
엄동전력
GUANGDONG ELECTRIC POWER
2014年
2期
65-69
,共5页
郑茂然%曾铁军%唐亚男%苏泽光
鄭茂然%曾鐵軍%唐亞男%囌澤光
정무연%증철군%당아남%소택광
电流互感器断线%3/2 接线%母线差动保护%快速闭锁
電流互感器斷線%3/2 接線%母線差動保護%快速閉鎖
전류호감기단선%3/2 접선%모선차동보호%쾌속폐쇄
CT break line%3/2 wiring%busbar differential protection%rapid interlock
西北电网线路长,支路少,3/2接线系统实际投入运行的母线少,当电流互感器(current transformer, CT)断线和短路故障相继发生时间差在5 s内时,断线慢速闭锁差动判据由于5 s延时而不能闭锁CT断线而引起差动误动,针对该问题,分析了CT断线的典型特征,提出可以用差流上升、制动电流下降作为3/2断路器接线CT断线快速闭锁母线差动保护的判据、判据的3种情况及其实现。仿真验证表明,该判据在不影响差动保护快速性的同时,能有效地识别CT断线,进而闭锁母线差动保护,经多次静、动模试验验证,该判据能正确动作,可用于传统及数字化后的双母接线母线差动、变压器差动、发电机差动等电流差动保护。
西北電網線路長,支路少,3/2接線繫統實際投入運行的母線少,噹電流互感器(current transformer, CT)斷線和短路故障相繼髮生時間差在5 s內時,斷線慢速閉鎖差動判據由于5 s延時而不能閉鎖CT斷線而引起差動誤動,針對該問題,分析瞭CT斷線的典型特徵,提齣可以用差流上升、製動電流下降作為3/2斷路器接線CT斷線快速閉鎖母線差動保護的判據、判據的3種情況及其實現。倣真驗證錶明,該判據在不影響差動保護快速性的同時,能有效地識彆CT斷線,進而閉鎖母線差動保護,經多次靜、動模試驗驗證,該判據能正確動作,可用于傳統及數字化後的雙母接線母線差動、變壓器差動、髮電機差動等電流差動保護。
서북전망선로장,지로소,3/2접선계통실제투입운행적모선소,당전류호감기(current transformer, CT)단선화단로고장상계발생시간차재5 s내시,단선만속폐쇄차동판거유우5 s연시이불능폐쇄CT단선이인기차동오동,침대해문제,분석료CT단선적전형특정,제출가이용차류상승、제동전류하강작위3/2단로기접선CT단선쾌속폐쇄모선차동보호적판거、판거적3충정황급기실현。방진험증표명,해판거재불영향차동보호쾌속성적동시,능유효지식별CT단선,진이폐쇄모선차동보호,경다차정、동모시험험증,해판거능정학동작,가용우전통급수자화후적쌍모접선모선차동、변압기차동、발전궤차동등전류차동보호。
Circuits of northwestern power grid are long with few branches and busbar for practical operation of 3/2 wiring system are few,too.When current transformer break line and short circuit fault happening in succession within 5 seconds, for reason of 5 seconds delay,break line slow interlock differential criterion is not able to cause CT break line interlock which may result in differential misfunction.Aiming at the above problem,this paper analyzes typical characteristic of CT break line and proposes to take difference streak rise and braking current decrease as criterion for rapid interlock busbar dif-ferential protection for 3/2 breaker wiring CT break line.In addition,it proposes three conditions of the criterion and reali-zation ways.Simulation verification indicates that this criterion is able to effectively identify CT break line at the same time of not affecting rapidity of differential protection,and then it is able to interlock bus differential protection.By several times of testing and verification,it proves that the criterion is able to act correctly and used for current differential protec-tion such as traditional and after-digital double-bus wiring differential protection,transformer differential protection and generator differential protection.