段炼%江安烽%傅正财%魏本刚
段煉%江安烽%傅正財%魏本剛
단련%강안봉%부정재%위본강
特高压交流变电站%直流偏磁%超/特高压直流线路%多回直流线路%串联电阻
特高壓交流變電站%直流偏磁%超/特高壓直流線路%多迴直流線路%串聯電阻
특고압교류변전참%직류편자%초/특고압직류선로%다회직류선로%천련전조
UHVAC substation%DC biasing%EHV and UHVDC transmission line%multi HVDC lines%series resistor
研究了上海周边7条超高压与特高压直流系统中有一条或多条线路单极运行时,上海沪西等特高压变电站和上海500 kV电网的直流偏磁情况。电磁仿真计算各交流变电站的地电位分布与中性点偏磁电流,结果表明:多条直流线路单极运行时一条线路上的电流不会通过其他线路回流,特高压变电站的直流电流在多条线路同时单极运行时的数值等于单条线路单极运行时的代数和,向家坝-上海、锦屏-苏南、三峡-上海这3条线路单极运行时对沪西变电站的影响最大,使特高压变压器中性点偏磁电流超过5 A,约2.4Ω的变压器中性点串联电阻可较好地抑制沪西特高压变电站的直流偏磁电流。
研究瞭上海週邊7條超高壓與特高壓直流繫統中有一條或多條線路單極運行時,上海滬西等特高壓變電站和上海500 kV電網的直流偏磁情況。電磁倣真計算各交流變電站的地電位分佈與中性點偏磁電流,結果錶明:多條直流線路單極運行時一條線路上的電流不會通過其他線路迴流,特高壓變電站的直流電流在多條線路同時單極運行時的數值等于單條線路單極運行時的代數和,嚮傢壩-上海、錦屏-囌南、三峽-上海這3條線路單極運行時對滬西變電站的影響最大,使特高壓變壓器中性點偏磁電流超過5 A,約2.4Ω的變壓器中性點串聯電阻可較好地抑製滬西特高壓變電站的直流偏磁電流。
연구료상해주변7조초고압여특고압직류계통중유일조혹다조선로단겁운행시,상해호서등특고압변전참화상해500 kV전망적직류편자정황。전자방진계산각교류변전참적지전위분포여중성점편자전류,결과표명:다조직류선로단겁운행시일조선로상적전류불회통과기타선로회류,특고압변전참적직류전류재다조선로동시단겁운행시적수치등우단조선로단겁운행시적대수화,향가패-상해、금병-소남、삼협-상해저3조선로단겁운행시대호서변전참적영향최대,사특고압변압기중성점편자전류초과5 A,약2.4Ω적변압기중성점천련전조가교호지억제호서특고압변전참적직류편자전류。
The DC magnetic biasing in Shanghai UHVAC substations and that in Shanghai 500 kV power network are researched when one or more in seven EHVDC and UHVDC power transmission lines around Shanghai are operated in monopole operation mode. Results of electromagnetic simulation on ground potential distributions in AC substations and biasing currents through neutral points show that when multi DC transmission lines are operated in monopole operation mode, the current of one line will not backflow via other lines; when multi DC lines are operated in monopole mode simultaneously, the value of DC current biasing in UHVAC substations is equal to algebraic sum of the DC current biasing of each DC line solely operated in monopole mode;the most serious impact on the West Shanghai UHVAC substation is caused by monopole operation mode of three EHVDC and UHVDC lines, namely the EHVDC transmission line from Three Gorges to Shanghai, the UHVDC transmission line from Xiangjiaba to Shanghai and the UHVDC transmission line from Jinping to Suzhou, and it makes the DC biasing current at neutral point exceeding over 5 A; the transformer neutral point series-resistor with the value about 2.4 ohm can suppress the DC magnetic biasing current in West Shanghai UHVAC substation better.