对重庆地区某办公楼的地埋管地源热泵系统进行了经济性和节能性分析,其中节能性分析是依据测试结果进行的。经济性分析结果表明:本工程采用地埋管地源热泵系统,相比空气源热泵系统,初投资静态回收期为12年;相比冷水机组+燃气锅炉,初投资静态回收期为14.1年。节能性分析结果表明:本工程采用地埋管地源热泵系统,系统制冷和制热能效比分别能达到3.6和2.9;夏季,相比于空气源热泵,系统能效提高率为20.0%,相比于冷水机组,系统能效提高率为2.9%;冬季,相比于空气源热泵,系统能效提高率为16.0%,相比于燃气锅炉,系统能效提高率为26.7%。
對重慶地區某辦公樓的地埋管地源熱泵繫統進行瞭經濟性和節能性分析,其中節能性分析是依據測試結果進行的。經濟性分析結果錶明:本工程採用地埋管地源熱泵繫統,相比空氣源熱泵繫統,初投資靜態迴收期為12年;相比冷水機組+燃氣鍋爐,初投資靜態迴收期為14.1年。節能性分析結果錶明:本工程採用地埋管地源熱泵繫統,繫統製冷和製熱能效比分彆能達到3.6和2.9;夏季,相比于空氣源熱泵,繫統能效提高率為20.0%,相比于冷水機組,繫統能效提高率為2.9%;鼕季,相比于空氣源熱泵,繫統能效提高率為16.0%,相比于燃氣鍋爐,繫統能效提高率為26.7%。
대중경지구모판공루적지매관지원열빙계통진행료경제성화절능성분석,기중절능성분석시의거측시결과진행적。경제성분석결과표명:본공정채용지매관지원열빙계통,상비공기원열빙계통,초투자정태회수기위12년;상비랭수궤조+연기과로,초투자정태회수기위14.1년。절능성분석결과표명:본공정채용지매관지원열빙계통,계통제랭화제열능효비분별능체도3.6화2.9;하계,상비우공기원열빙,계통능효제고솔위20.0%,상비우랭수궤조,계통능효제고솔위2.9%;동계,상비우공기원열빙,계통능효제고솔위16.0%,상비우연기과로,계통능효제고솔위26.7%。
This paper analysis the economic and energy efficiency of the ground source heat pump system of an office building in Chongqing, in which the energy efficiency analysis is based on the test results. Economic analysis shows that:compared to the air-source heat pump system, the static payback period of the initial investment is 12 years;compared to the water chiller+gas boiler system, the static payback period of the initial investment is 14.1 years. Energy efficiency analysis shows that:the cooling and heating energy efficiency of the ground source heat pump system can reach 3.6 and 2.9 respectively;in summer, the system efficiency is increased by 20.0%compared to the air-source heat pump system and 2.9%compared to the water chiller;in winter, the system efficiency is increased by 16.0%compared to the air-source heat pump system and 26.7%compared to the gas boiler.