介绍了一起由于导电杆未安装到位,致使导电杆与触指接触不良,触头发热熔化,最终造成母线导体对外壳放电的单相接地短路故障。通过对气体绝缘全封闭组合电器(GIS)接头结构的分析,对GIS触头连接不良缺陷的早期发现与交接试验提出了建议。
介紹瞭一起由于導電桿未安裝到位,緻使導電桿與觸指接觸不良,觸頭髮熱鎔化,最終造成母線導體對外殼放電的單相接地短路故障。通過對氣體絕緣全封閉組閤電器(GIS)接頭結構的分析,對GIS觸頭連接不良缺陷的早期髮現與交接試驗提齣瞭建議。
개소료일기유우도전간미안장도위,치사도전간여촉지접촉불량,촉두발열용화,최종조성모선도체대외각방전적단상접지단로고장。통과대기체절연전봉폐조합전기(GIS)접두결구적분석,대GIS촉두련접불량결함적조기발현여교접시험제출료건의。
A ground fault arisen by the poor contact is introduced in this paper. Because the installation of the conducting rod was not in place, the bad contact leads to the heating and melting of the contacts, resulting in the single-phase ground fault. Based on the analysis of the structure of GIS contact, several proposals are put forward for the early detection of the bad contacts of GIS and the handing over test.