梁静%赵青春%于冰%胡立锦%赵伟%常喜强
樑靜%趙青春%于冰%鬍立錦%趙偉%常喜彊
량정%조청춘%우빙%호립금%조위%상희강
对称故障%负荷%高频保护%仿真分析%离线模拟
對稱故障%負荷%高頻保護%倣真分析%離線模擬
대칭고장%부하%고빈보호%방진분석%리선모의
symmetrical fault%load%high-frequency protection%simulation analysis%off-line simulation
提出了由于电网结构差异较大,负荷结构和电源布局不均匀导致线路区外对称故障时可能出现较大的零序电流,进而导致线路高频保护误动作的思考。理论推导了对称故障下出现零序电流的原因,在此基础上搭建了仿真模型进行仿真。理论分析和仿真结果表明线路系统区外对称故障下零序电流的最大确实会导致被保护线路高频保护误动。以新疆某地区实际电网为模型,沿用系统参数设置,采用在线和离线的方法调节系统负荷及电源投入情况,模拟并分析出现的高频保护误动情况,进而针对模拟情况提出合理的预防建议和措施。
提齣瞭由于電網結構差異較大,負荷結構和電源佈跼不均勻導緻線路區外對稱故障時可能齣現較大的零序電流,進而導緻線路高頻保護誤動作的思攷。理論推導瞭對稱故障下齣現零序電流的原因,在此基礎上搭建瞭倣真模型進行倣真。理論分析和倣真結果錶明線路繫統區外對稱故障下零序電流的最大確實會導緻被保護線路高頻保護誤動。以新疆某地區實際電網為模型,沿用繫統參數設置,採用在線和離線的方法調節繫統負荷及電源投入情況,模擬併分析齣現的高頻保護誤動情況,進而針對模擬情況提齣閤理的預防建議和措施。
제출료유우전망결구차이교대,부하결구화전원포국불균균도치선로구외대칭고장시가능출현교대적령서전류,진이도치선로고빈보호오동작적사고。이론추도료대칭고장하출현령서전류적원인,재차기출상탑건료방진모형진행방진。이론분석화방진결과표명선로계통구외대칭고장하령서전류적최대학실회도치피보호선로고빈보호오동。이신강모지구실제전망위모형,연용계통삼수설치,채용재선화리선적방법조절계통부하급전원투입정황,모의병분석출현적고빈보호오동정황,진이침대모의정황제출합리적예방건의화조시。
A stronger zero-sequence current may occur when the symmetrical fault appears outside the line zone due to the different structure of power grid, uneven load structure and power distribution, which results in the misoperation of high -frequencyprotection.The reasons why zero -sequence current occurs under symmetrical fault are analyzed by theoretical deriva -tion, and the simulation model is established.The theoretical analysis and simulation results show that the maximum zero -sequencecurrent under symmetrical fault outside the line zone will exactly cause the misoperation of high -frequency protectionin the protected line.Taking the actual power grid as the model in one place of Xinjiang , the misoperation of high -frequencyprotection is simulated and analyzed by following the setting of system parameters and adopting the on -line and off -linemethods to control the system load and the power source connection , thus the reasonable preventive suggestions and measuresare put forward.