依某直流系统功率调制异常为例,结合现场相关事件记录和故障恢复前后时刻录波波形,分析推断引起此次功率调节异常原因是整流侧接收到对站电流参考值出现异常。详细分析了总的功率参考值、总的电流参考值、直流电流参考值、直流电流测量值之间数值计算关系,以及现场极控系统站间通信完成功能,分析定位造成整流侧电流参考值异常原因是换流站站间通信通道存在异常。仿照现场极控系统实际站间通信配置结构,设计仿真实验项目,在实验室搭建的仿真平台上完成现场故障重现,完成推论验证。最后,总结分析造成直流系统功率调制异常相关环节并指出对应处理措施,对今后功率调制相关故障快速处理具有实际指导意义。
依某直流繫統功率調製異常為例,結閤現場相關事件記錄和故障恢複前後時刻錄波波形,分析推斷引起此次功率調節異常原因是整流側接收到對站電流參攷值齣現異常。詳細分析瞭總的功率參攷值、總的電流參攷值、直流電流參攷值、直流電流測量值之間數值計算關繫,以及現場極控繫統站間通信完成功能,分析定位造成整流側電流參攷值異常原因是換流站站間通信通道存在異常。倣照現場極控繫統實際站間通信配置結構,設計倣真實驗項目,在實驗室搭建的倣真平檯上完成現場故障重現,完成推論驗證。最後,總結分析造成直流繫統功率調製異常相關環節併指齣對應處理措施,對今後功率調製相關故障快速處理具有實際指導意義。
의모직류계통공솔조제이상위례,결합현장상관사건기록화고장회복전후시각록파파형,분석추단인기차차공솔조절이상원인시정류측접수도대참전류삼고치출현이상。상세분석료총적공솔삼고치、총적전류삼고치、직류전류삼고치、직류전류측량치지간수치계산관계,이급현장겁공계통참간통신완성공능,분석정위조성정류측전류삼고치이상원인시환류참참간통신통도존재이상。방조현장겁공계통실제참간통신배치결구,설계방진실험항목,재실험실탑건적방진평태상완성현장고장중현,완성추론험증。최후,총결분석조성직류계통공솔조제이상상관배절병지출대응처리조시,대금후공솔조제상관고장쾌속처리구유실제지도의의。
According to an HVDC system power modulation abnormal case, this paper analyzes the power abnormal modulation reason that the rectifier station receives the abnormal current reference from the other station based on the related events and recorded waveform before and after fault recovery. From the detailed analysis of the relationship among the total power reference, the total current reference, the DC current reference, the measured DC current value, and the role of the pole control DUST between the two stations, the inference which causing the abnormal current reference is the abnormal communication channel of the pole control between the two stations. The simulation projects are designed and reappeared in the simulation platform built in the laboratory according to the actual structure of the inter-station communication configuration. At last, it summarizes the related links which cause abnormal power modulation and gives corresponding treatments, which has guiding significance for similar power modulation fast processing in the HVDC system.