常鲜戎%王辉云%郭一杰%杨永华
常鮮戎%王輝雲%郭一傑%楊永華
상선융%왕휘운%곽일걸%양영화
配电网静止同步补偿器%软件优化%补偿滞后%谐波抑制%无功补偿
配電網靜止同步補償器%軟件優化%補償滯後%諧波抑製%無功補償
배전망정지동보보상기%연건우화%보상체후%해파억제%무공보상
D-STATCOM%software optimization%compensation delay%harmonic suppression%reactive power compensation
控制延时会导致配电网静止同步补偿器(D-STATCOM)对谐波抑制和无功补偿的精度降低。为改善传统控制策略滞后时间长、补偿效果差的缺点,提出了一种基于软件优化的新型控制策略。通过对D-STATCOM补偿指令电流的特性进行分析,对软件流程进行相应调整,缩短了谐波和无功补偿指令电流的计算延时,使补偿滞后大大减少,谐波抑制和无功补偿的精度得到明显提高。该策略无需复杂算法,实现简单、有效。在Matlab/Simulink环境中进行了仿真分析,并且研制了一台容量为10 kVA的三相四线制D-STATCOM实验样机进行验证,结果证明了新型控制策略的正确性和可行性。
控製延時會導緻配電網靜止同步補償器(D-STATCOM)對諧波抑製和無功補償的精度降低。為改善傳統控製策略滯後時間長、補償效果差的缺點,提齣瞭一種基于軟件優化的新型控製策略。通過對D-STATCOM補償指令電流的特性進行分析,對軟件流程進行相應調整,縮短瞭諧波和無功補償指令電流的計算延時,使補償滯後大大減少,諧波抑製和無功補償的精度得到明顯提高。該策略無需複雜算法,實現簡單、有效。在Matlab/Simulink環境中進行瞭倣真分析,併且研製瞭一檯容量為10 kVA的三相四線製D-STATCOM實驗樣機進行驗證,結果證明瞭新型控製策略的正確性和可行性。
공제연시회도치배전망정지동보보상기(D-STATCOM)대해파억제화무공보상적정도강저。위개선전통공제책략체후시간장、보상효과차적결점,제출료일충기우연건우화적신형공제책략。통과대D-STATCOM보상지령전류적특성진행분석,대연건류정진행상응조정,축단료해파화무공보상지령전류적계산연시,사보상체후대대감소,해파억제화무공보상적정도득도명현제고。해책략무수복잡산법,실현간단、유효。재Matlab/Simulink배경중진행료방진분석,병차연제료일태용량위10 kVA적삼상사선제D-STATCOM실험양궤진행험증,결과증명료신형공제책략적정학성화가행성。
Control delay significantly affects the performance of distribution static synchronous compensator (D-STATCOM) in harmonic suppression and reactive power compensation. To overcome the drawback of the conventional control method, which has long compensation delay and low compensation accuracy, a novel control strategy based on software optimization is proposed. Software flow is adjusted based on the analysis of the reference compensation currents. It shortens the calculation delay of harmonics and reactive power compensation reference current, so compensation delay occurs less and compensation accuracy of harmonic suppression and reactive power compensation is improved. Results obtained by D-STATCOM simulations system built in Matlab/Simulink and prototype experiment of a 10 kVA three-phase four-wire D-STATCOM show the validity and feasibility of the proposed strategy.