某核电站旋转滤网阴极保护系统出现异常波动,且局部处于非保护状态,对阴极保护系统及被保护设备特点分析,结果显示被保护设备表面电化学状态不均匀是导致阴极保护系统失效的根本原因,并给出改变阴极保护设计及运行模式两种改进措施,为类似机组提供参考。
某覈電站鏇轉濾網陰極保護繫統齣現異常波動,且跼部處于非保護狀態,對陰極保護繫統及被保護設備特點分析,結果顯示被保護設備錶麵電化學狀態不均勻是導緻陰極保護繫統失效的根本原因,併給齣改變陰極保護設計及運行模式兩種改進措施,為類似機組提供參攷。
모핵전참선전려망음겁보호계통출현이상파동,차국부처우비보호상태,대음겁보호계통급피보호설비특점분석,결과현시피보호설비표면전화학상태불균균시도치음겁보호계통실효적근본원인,병급출개변음겁보호설계급운행모식량충개진조시,위유사궤조제공삼고。
Abnormal fluctuations were found in the cathodic protection system of a rotating filter in the nuclear power plant, and part of the rotating filter was under unprotected state. Analyze on the characteristics of cathodic protection system displayed that the root cause was the uneven electrochemical state on the surface of the protected equipment. Two methods were provided for improving the situation:changing cathodic protection system design or operation mode.