建筑科学与工程学报
建築科學與工程學報
건축과학여공정학보
JOURNAL OF ARCHITECTURE AND CIVIL ENGINEERING
2014年
1期
76-82
,共7页
高层建筑%风洞试验%风压分布%风压系数%等效静力风荷载
高層建築%風洞試驗%風壓分佈%風壓繫數%等效靜力風荷載
고층건축%풍동시험%풍압분포%풍압계수%등효정력풍하재
high-rise building%wind tunnel test%wind pressure distribution%wind pressure coef-ficient%equivalent static wind load
以成都某复杂体型超高层建筑为研究对象,在大气边界层风洞中对其进行了单体建筑刚性模型测压试验,对模型表面风压的分布规律进行了讨论;利用随机振动理论在频域内计算了基础等效静力风荷载和结构顶部加速度响应,并将风荷载试验结果与中、日两国最新规范的计算结果进行对比分析。结果表明:复杂体型高层建筑表面风压的分布规律与常规截面高层建筑基本保持一致,但是受到建筑体型的影响,个别立面的风压分布会出现与中国规范规定值完全相反的结论;同时,在局部区域会出现比规范值偏大的结果,由风洞试验结果计算得到的顺风向基底剪力和弯矩均大于中、日两国规范的计算结果,且日本规范的计算结果要大于中国规范的计算结果。所得结论可为类似工程提供参考。
以成都某複雜體型超高層建築為研究對象,在大氣邊界層風洞中對其進行瞭單體建築剛性模型測壓試驗,對模型錶麵風壓的分佈規律進行瞭討論;利用隨機振動理論在頻域內計算瞭基礎等效靜力風荷載和結構頂部加速度響應,併將風荷載試驗結果與中、日兩國最新規範的計算結果進行對比分析。結果錶明:複雜體型高層建築錶麵風壓的分佈規律與常規截麵高層建築基本保持一緻,但是受到建築體型的影響,箇彆立麵的風壓分佈會齣現與中國規範規定值完全相反的結論;同時,在跼部區域會齣現比規範值偏大的結果,由風洞試驗結果計算得到的順風嚮基底剪力和彎矩均大于中、日兩國規範的計算結果,且日本規範的計算結果要大于中國規範的計算結果。所得結論可為類似工程提供參攷。
이성도모복잡체형초고층건축위연구대상,재대기변계층풍동중대기진행료단체건축강성모형측압시험,대모형표면풍압적분포규률진행료토론;이용수궤진동이론재빈역내계산료기출등효정력풍하재화결구정부가속도향응,병장풍하재시험결과여중、일량국최신규범적계산결과진행대비분석。결과표명:복잡체형고층건축표면풍압적분포규률여상규절면고층건축기본보지일치,단시수도건축체형적영향,개별립면적풍압분포회출현여중국규범규정치완전상반적결론;동시,재국부구역회출현비규범치편대적결과,유풍동시험결과계산득도적순풍향기저전력화만구균대우중、일량국규범적계산결과,차일본규범적계산결과요대우중국규범적계산결과。소득결론가위유사공정제공삼고。
Based on the wind tunnel test of the rigid model of a complex shape high-rise building in Chengdu in the atmospheric boundary layer ,the surface wind pressure distribution laws of model were discussed .The equivalent static wind loads and wind-induced acceleration responses of top structure were calculated based on the wind tunnel results and compared with those estimated from Chinese and Japanese building design codes by using random vibration theory calculations of the model in the frequency domain . The results show that surface wind pressure distribution characteristics of complex shape high-rise building are coincided with those of conventional cross-section high-rise building .But the individual facade and normative pressure distribution results will appear the opposite conclusions owing to building size impacting .Meanwhile ,in the local area ,test results will be larger than the standard value results .The downwind base shear and bending moment calculated by the wind tunnel test results are greater than that by Chinese and Japanese codes ,and calculation results of Japanese code are bigger than those of Chinese code . The conclusions obtained in the paper can provide reference for structural design of similar pro-jects .