浙江电力
浙江電力
절강전력
ZHEJIANG ELECTRIC POWER
2014年
3期
35-37,62
,共4页
潘益伟%陈建胜%林坚%金佳敏
潘益偉%陳建勝%林堅%金佳敏
반익위%진건성%림견%금가민
开关柜%套管%放电%防范措施
開關櫃%套管%放電%防範措施
개관거%투관%방전%방범조시
switch cabinet%bushing%discharging%preventive measures
对一起40.5 kV开关柜放电的原因进行了分析,对2种不同结构套管的电场分布进行了仿真,证明不带屏蔽套管周围空气中,电场强度大,均匀性差,更易发生局部放电。对导致开关柜放电的其他因素也进行了总结,提出切实可行的防范措施。
對一起40.5 kV開關櫃放電的原因進行瞭分析,對2種不同結構套管的電場分佈進行瞭倣真,證明不帶屏蔽套管週圍空氣中,電場彊度大,均勻性差,更易髮生跼部放電。對導緻開關櫃放電的其他因素也進行瞭總結,提齣切實可行的防範措施。
대일기40.5 kV개관거방전적원인진행료분석,대2충불동결구투관적전장분포진행료방진,증명불대병폐투관주위공기중,전장강도대,균균성차,경역발생국부방전。대도치개관거방전적기타인소야진행료총결,제출절실가행적방범조시。
This paper analyzes the reason of discharging in 40.5 kV switch cabinet and simulates the electric field distribution of two bushing with different structures. It is proved that the screen-free bushing has strong electric field strength and poor uniformity in the air , and hence partial discharge can easily happen. The pa-per also summarizes other factors causing discharge of switch cabinet and summarizes practical and feasible preventive measures.