翁华%徐政%许烽%屠卿瑞%董桓锋
翁華%徐政%許烽%屠卿瑞%董桓鋒
옹화%서정%허봉%도경서%동환봉
紧急功率支援%限制因素%准稳态模型%多直流送出系统%电压波动
緊急功率支援%限製因素%準穩態模型%多直流送齣繫統%電壓波動
긴급공솔지원%한제인소%준은태모형%다직류송출계통%전압파동
emergency power support%constraint factor%quasi-steady model%multi-send HVDC systems%voltage fluctuation
为了保证直流系统在紧急功率支援时能有效提升实际输送功率,有必要分析直流系统实际输送功率受直流换流站交流母线电压波动的影响情况。在理论分析时直流系统采用了准稳态模型,然后根据直流系统Ud-Id特性曲线分析得到直流系统的各种可能的运行模式受两端换流站交流母线电压的影响情况,最后针对每种模式计算得到此时直流系统的实际输送功率。仿真结果表明,理论分析得到的直流系统实际输送功率受两端换流站交流母线电压的制约情况与PSCAD/EMTDC 中直流系统详细模型的仿真结果一致。研究结果表明,只有两端换流站交流母线电压维持在一定电压水平,才能使直流系统实际输送功率达到紧急功率支援指令值。
為瞭保證直流繫統在緊急功率支援時能有效提升實際輸送功率,有必要分析直流繫統實際輸送功率受直流換流站交流母線電壓波動的影響情況。在理論分析時直流繫統採用瞭準穩態模型,然後根據直流繫統Ud-Id特性麯線分析得到直流繫統的各種可能的運行模式受兩耑換流站交流母線電壓的影響情況,最後針對每種模式計算得到此時直流繫統的實際輸送功率。倣真結果錶明,理論分析得到的直流繫統實際輸送功率受兩耑換流站交流母線電壓的製約情況與PSCAD/EMTDC 中直流繫統詳細模型的倣真結果一緻。研究結果錶明,隻有兩耑換流站交流母線電壓維持在一定電壓水平,纔能使直流繫統實際輸送功率達到緊急功率支援指令值。
위료보증직류계통재긴급공솔지원시능유효제승실제수송공솔,유필요분석직류계통실제수송공솔수직류환류참교류모선전압파동적영향정황。재이론분석시직류계통채용료준은태모형,연후근거직류계통Ud-Id특성곡선분석득도직류계통적각충가능적운행모식수량단환류참교류모선전압적영향정황,최후침대매충모식계산득도차시직류계통적실제수송공솔。방진결과표명,이론분석득도적직류계통실제수송공솔수량단환류참교류모선전압적제약정황여PSCAD/EMTDC 중직류계통상세모형적방진결과일치。연구결과표명,지유량단환류참교류모선전압유지재일정전압수평,재능사직류계통실제수송공솔체도긴급공솔지원지령치。
ABSTRACT:To guarantee that the high voltage direct current (HVDC) system is able to raise the transmission power effectively in the case of emergency power support, it is necessary to analyze the impact of the voltage fluctuation of HVDC converter AC bus on the DC transmission power. The HVDC quasi-steady model was adopted for theoretical analyzing in this paper, then the operating mode of the HVDC system varying with HVDC converter AC bus voltages at both ends was obtained according to the HVDC Ud-Id characteristic curve, and finally the actual transmission power of the HVDC system for each possible operating mode was calculated. The simulation results show that the theoretical analysis result of the transmission power of HVDC limited by the varying of HVDC converter AC bus voltages was consistent with that of the simulation with a detail HVDC model in PSCAD/EMTDC. The research results show that in emergency, only when the HVDC converter AC bus voltages at both ends maintain at a certain voltage level, can the actual transmission power of the HVDC system follow the order of emergency power support reference.