直流偏磁%电流互感器%差动保护%和应涌流
直流偏磁%電流互感器%差動保護%和應湧流
직류편자%전류호감기%차동보호%화응용류
DC magnetic bias%TA saturation%differential protection%sympathetic inrush
由地磁感应电流(GIC)/高压直流输电单极大地回路运行方式引发的直流偏磁会对电磁式电流互感器(TA)的传变特性产生影响,计及直流偏磁影响的TA饱和与无偏磁时相比具有一定的特殊性,会对变压器差动保护产生影响。通过构建考虑直流偏磁的交流系统仿真模型,研究了TA起始饱和时间受直流偏磁的影响及其对变压器差动保护的影响。指出了直流偏磁是TA局部暂态饱和的诱因之一,并通过对直流偏磁条件下和应涌流的仿真研究,分析了TA局部暂态饱和对变压器差动保护的影响。研究结果表明,直流偏磁可能会加速TA饱和,防止区外故障TA饱和引起差动保护误动的时差法判据将受到考验;而直流偏磁诱发的TA局部暂态饱和则可能引起变压器差动保护的误动。
由地磁感應電流(GIC)/高壓直流輸電單極大地迴路運行方式引髮的直流偏磁會對電磁式電流互感器(TA)的傳變特性產生影響,計及直流偏磁影響的TA飽和與無偏磁時相比具有一定的特殊性,會對變壓器差動保護產生影響。通過構建攷慮直流偏磁的交流繫統倣真模型,研究瞭TA起始飽和時間受直流偏磁的影響及其對變壓器差動保護的影響。指齣瞭直流偏磁是TA跼部暫態飽和的誘因之一,併通過對直流偏磁條件下和應湧流的倣真研究,分析瞭TA跼部暫態飽和對變壓器差動保護的影響。研究結果錶明,直流偏磁可能會加速TA飽和,防止區外故障TA飽和引起差動保護誤動的時差法判據將受到攷驗;而直流偏磁誘髮的TA跼部暫態飽和則可能引起變壓器差動保護的誤動。
유지자감응전류(GIC)/고압직류수전단겁대지회로운행방식인발적직류편자회대전자식전류호감기(TA)적전변특성산생영향,계급직류편자영향적TA포화여무편자시상비구유일정적특수성,회대변압기차동보호산생영향。통과구건고필직류편자적교류계통방진모형,연구료TA기시포화시간수직류편자적영향급기대변압기차동보호적영향。지출료직류편자시TA국부잠태포화적유인지일,병통과대직류편자조건하화응용류적방진연구,분석료TA국부잠태포화대변압기차동보호적영향。연구결과표명,직류편자가능회가속TA포화,방지구외고장TA포화인기차동보호오동적시차법판거장수도고험;이직류편자유발적TA국부잠태포화칙가능인기변압기차동보호적오동。
The transferring characteristics of current transformers(TA) are subject to possible changes due to DC magnetic bias caused by geomagnetic induced current(GIC)/high voltage direct current(HVDC).The particularity of TA saturation affected by the DC magnetic bias will severely impact the transformer differential protection system.Based on the AC system simulation models considering DC magnetic bias,the effects caused by the variation of time-to-saturation of protective TAs are studied.Moreover,studies show that DC magnetic bias will lead to TA partial transient saturation.According to simulation of sympathetic inrush with DC magnetic bias,this paper analyzes the impacts on differential protection resulting from the TA partial transient saturation.The research demonstrates that DC magnetic bias may accelerate saturation of protective TAs.This is a challenge to the method of locating the time difference used for preventing maloperation due to TA saturation when external faults occurred.The research also shows that TA partial transient saturation caused by DC magnetic bias may contribute to maloperation of transformer differential protection.