针对某110 kV变电站2号主变压器油色谱监测数据异常情况,从油色谱试验、电气试验、吊罩检查三方面进行分析,认为铁心片间短路是故障的主要原因,提出加强油道之间的绝缘撑条、更换铁心片等处理措施及建议。
針對某110 kV變電站2號主變壓器油色譜鑑測數據異常情況,從油色譜試驗、電氣試驗、弔罩檢查三方麵進行分析,認為鐵心片間短路是故障的主要原因,提齣加彊油道之間的絕緣撐條、更換鐵心片等處理措施及建議。
침대모110 kV변전참2호주변압기유색보감측수거이상정황,종유색보시험、전기시험、조조검사삼방면진행분석,인위철심편간단로시고장적주요원인,제출가강유도지간적절연탱조、경환철심편등처리조시급건의。
Aiming at the oil chromatogram abnormal condition monitoring data of 110 kV transformer substation No 2. main transformer ,analyzes from three aspects of oil chromato-graphic test ,electrical test ,eepot overhaul ,considers that core short circuit is the main reason ,proposes the settle-ments suggessions that are to enhance the insulation between the oil channel support bar ,to replace laminations and so on .