输电线路导线覆冰严重威胁电力系统的安全运行,对型线和普通绞线覆冰过程及其特性开展深入研究可为电网输电线路防覆冰技术和瓦型导线的推广应用提供参考。在人工气候室内模拟自然覆冰条件,对LGJ-185/10、LGJ-400/65型普通绞线和JNRLH60X/LBIA-185/30、Drake 1020型瓦型导线进行了试验研究,分析了2类导线覆冰异同。结果表明:在相同覆冰条件下,瓦型导线的覆冰厚度比相同直径的普通绞线大,冰棱长度则反之;直径较小的导线覆冰厚度要比直径较大的同种导线覆冰厚度增长更快,而冰棱增长则相对较慢;其他覆冰条件相同时温度越低或者风速越大,瓦型导线和普通绞线的覆冰厚度差异越明显。
輸電線路導線覆冰嚴重威脅電力繫統的安全運行,對型線和普通絞線覆冰過程及其特性開展深入研究可為電網輸電線路防覆冰技術和瓦型導線的推廣應用提供參攷。在人工氣候室內模擬自然覆冰條件,對LGJ-185/10、LGJ-400/65型普通絞線和JNRLH60X/LBIA-185/30、Drake 1020型瓦型導線進行瞭試驗研究,分析瞭2類導線覆冰異同。結果錶明:在相同覆冰條件下,瓦型導線的覆冰厚度比相同直徑的普通絞線大,冰稜長度則反之;直徑較小的導線覆冰厚度要比直徑較大的同種導線覆冰厚度增長更快,而冰稜增長則相對較慢;其他覆冰條件相同時溫度越低或者風速越大,瓦型導線和普通絞線的覆冰厚度差異越明顯。
수전선로도선복빙엄중위협전력계통적안전운행,대형선화보통교선복빙과정급기특성개전심입연구가위전망수전선로방복빙기술화와형도선적추엄응용제공삼고。재인공기후실내모의자연복빙조건,대LGJ-185/10、LGJ-400/65형보통교선화JNRLH60X/LBIA-185/30、Drake 1020형와형도선진행료시험연구,분석료2류도선복빙이동。결과표명:재상동복빙조건하,와형도선적복빙후도비상동직경적보통교선대,빙릉장도칙반지;직경교소적도선복빙후도요비직경교대적동충도선복빙후도증장경쾌,이빙릉증장칙상대교만;기타복빙조건상동시온도월저혹자풍속월대,와형도선화보통교선적복빙후도차이월명현。
Transmission line icing is a serious threat to the safe operation of power systems. Therefore, comparative study on icing performance of T-type wire and ordinary stranded wire can provide a reference for power transmission line anti-icing technology and the application of T-type wire. We experimentally investigated four kinds of conductor, namely, LGJ-185/10, LGJ-400/65, JNRI.H60X/LBIA-185/30 and Drake 1020 in the artificial climate chamber. According to the test results, we find that, under the same environmental parameters, the ice thickness of T-type wire is higher than that of the same diameter ordinary stranded wire, but the situation of icicle length is opposite. As for the same kind of wire, the shorter wire diameter is, the faster the ice thickness grows, whereas, the situation of icicle length is the opposite. Under the same icing conditions, the lower the temperature or wind speed is, the more obvious differences of ice thickness between T-type wire and ordinary stranded wire are.