电力系统保护与控制
電力繫統保護與控製
전력계통보호여공제
POWER SYSTM PROTECTION AND CONTROL
2014年
1期
149-153
,共5页
吴水兰%宋小会%刘洋%郭志忠%蔡常群
吳水蘭%宋小會%劉洋%郭誌忠%蔡常群
오수란%송소회%류양%곽지충%채상군
变压器%后备保护%两相短路故障%保护灵敏度%保护整定
變壓器%後備保護%兩相短路故障%保護靈敏度%保護整定
변압기%후비보호%량상단로고장%보호령민도%보호정정
transformer%backup protection%two-phase short circuit fault%sensibility of protection%protection setting
就一例典型的变压器低压侧两相短路故障引起变压器高压侧后备保护先于低压侧后备保护动作的事故案例,分析了变压器低压侧两相短路故障时变压器高、低压侧电流的特性,并结合变压器低压侧其他故障情况,得出变压器高压侧后备保护和低压侧后备保护灵敏度的差异性。发现电力行业标准DL/T584-2007《3~110 kV电网继电保护装置运行整定规程》的规定不合适。特此对变压器后备保护整定提出一点建议:高压侧后备保护与低压侧后备保护的定值灵敏度要配合,且配合系数应不小于1.15。该建议有效提高了变压器高、低压侧后备保护的可靠性。
就一例典型的變壓器低壓側兩相短路故障引起變壓器高壓側後備保護先于低壓側後備保護動作的事故案例,分析瞭變壓器低壓側兩相短路故障時變壓器高、低壓側電流的特性,併結閤變壓器低壓側其他故障情況,得齣變壓器高壓側後備保護和低壓側後備保護靈敏度的差異性。髮現電力行業標準DL/T584-2007《3~110 kV電網繼電保護裝置運行整定規程》的規定不閤適。特此對變壓器後備保護整定提齣一點建議:高壓側後備保護與低壓側後備保護的定值靈敏度要配閤,且配閤繫數應不小于1.15。該建議有效提高瞭變壓器高、低壓側後備保護的可靠性。
취일례전형적변압기저압측량상단로고장인기변압기고압측후비보호선우저압측후비보호동작적사고안례,분석료변압기저압측량상단로고장시변압기고、저압측전류적특성,병결합변압기저압측기타고장정황,득출변압기고압측후비보호화저압측후비보호령민도적차이성。발현전역행업표준DL/T584-2007《3~110 kV전망계전보호장치운행정정규정》적규정불합괄。특차대변압기후비보호정정제출일점건의:고압측후비보호여저압측후비보호적정치령민도요배합,차배합계수응불소우1.15。해건의유효제고료변압기고、저압측후비보호적가고성。
Based on a typical case that the backup protection of high voltage side tripped earlier than the backup protection of low voltage side when two-phase short circuit fault took place at the transformer low voltage side, this paper analyzes the characteristics of the currents of high voltage side and low voltage side when two-phase short circuit fault takes place at the transformer low voltage side. Considering the situations of other kinds of faults at the transformer low voltage side, this paper finds out the difference of sensibility of backup protections between the high voltage side and low voltage side. The paper finds that the provision DL/T584-2007 3~110 kV operation setting regulations of relay protection equipments of power network in the standards of the power industry is inappropriate. Hereby, this paper gives an advice on the setting of transformer’s backup protection:the setting sensibility of backup protections of high voltage side must assort with that of the low voltage side, and the fit coefficient must be not less than 1.15.This proposal effectively promotes the reliability of transformer’s backup protection of high voltage side and low voltage side.