高电压技术
高電壓技術
고전압기술
HIGH VOLTAGE ENGINEERING
2012年
4期
855-862
,共8页
潘卓洪%张露%林进弟%文习山
潘卓洪%張露%林進弟%文習山
반탁홍%장로%림진제%문습산
多层水平土壤%地表电位%直流输电%直流分布%互阻%接地电阻
多層水平土壤%地錶電位%直流輸電%直流分佈%互阻%接地電阻
다층수평토양%지표전위%직류수전%직류분포%호조%접지전조
horizontal multi-layer soil%earth surface potectial(ESP)%HVDC transmission%DC distribution%mutual resistance%grounding resistance
直流输电入地电流在交流系统内分布,对变压器和电网造成不良影响。为探讨多层水平土壤情况下直流分布的规律,建立了直流分布的完整计算模型,通过数值计算分析了直流极的简化处理方法案和4层水平土壤对直流分布的影响。计算结果表明:在变电站距离大于10倍直流极尺寸的情况下可以用点电流源代替具体的直流极;场参数的求解是本模型关键,直流模型的场参数实质就是互阻,大型交流电网直流分布不能忽略变电站间互阻的影响;变电站接地电阻和地电位分布均受到大地参数作用呈现一致变化,但受影响程度不同,两者对交流电网总体直流分布的作用相反,造成直流分布呈现非线性变化;大地参数变化至一定程度时不会明显直流分布改变。
直流輸電入地電流在交流繫統內分佈,對變壓器和電網造成不良影響。為探討多層水平土壤情況下直流分佈的規律,建立瞭直流分佈的完整計算模型,通過數值計算分析瞭直流極的簡化處理方法案和4層水平土壤對直流分佈的影響。計算結果錶明:在變電站距離大于10倍直流極呎吋的情況下可以用點電流源代替具體的直流極;場參數的求解是本模型關鍵,直流模型的場參數實質就是互阻,大型交流電網直流分佈不能忽略變電站間互阻的影響;變電站接地電阻和地電位分佈均受到大地參數作用呈現一緻變化,但受影響程度不同,兩者對交流電網總體直流分佈的作用相反,造成直流分佈呈現非線性變化;大地參數變化至一定程度時不會明顯直流分佈改變。
직류수전입지전류재교류계통내분포,대변압기화전망조성불량영향。위탐토다층수평토양정황하직류분포적규률,건립료직류분포적완정계산모형,통과수치계산분석료직류겁적간화처리방법안화4층수평토양대직류분포적영향。계산결과표명:재변전참거리대우10배직류겁척촌적정황하가이용점전류원대체구체적직류겁;장삼수적구해시본모형관건,직류모형적장삼수실질취시호조,대형교류전망직류분포불능홀략변전참간호조적영향;변전참접지전조화지전위분포균수도대지삼수작용정현일치변화,단수영향정도불동,량자대교류전망총체직류분포적작용상반,조성직류분포정현비선성변화;대지삼수변화지일정정도시불회명현직류분포개변。
DC distribution in AC grid is caused by earth-return current of HVDC transmission.Adverse effect of transformer and AC grid is led by DC distribution.We established a complete model to analyze the laws of DC distribution under horizontal multi-layer soil,and used numerical methods to simplify the calculation of earth surface potential induced by DC electrode and to evaluate the DC distribution under 4-layer horizontal soil.The results reveal that,if any substation is away from 10 times as the DC electrode's dimension,the point source can be used as the specific DC electrode to obtain earth surface potential.Field parameter is the key point of the model while mutual resistance is the essence of field parameter.As to a large-scale power grid,mutual resistance can not be neglected.Soil parameters have the accordant influence on grounding resistance and ESP.But the influential degree is different.As grounding resistance and ESP has the adverse effect,DC distribution is nonlinear with grounding resistance and ESP.When soil parameters change to some extent,DC distribution is saturated.