张忠斌%杜垲%黄虎%张敬坤%潘亚梅
張忠斌%杜塏%黃虎%張敬坤%潘亞梅
장충빈%두개%황호%장경곤%반아매
制冷剂充注量%红外成像%微通道蒸发器%房间空调器%制冷性能
製冷劑充註量%紅外成像%微通道蒸髮器%房間空調器%製冷性能
제랭제충주량%홍외성상%미통도증발기%방간공조기%제랭성능
refrigerant charge%infrared thermographs%micro-channel evaporator%room air condi-tioner%cooling performance
在一台3HP分体落地式房间空调器壳体和风机等其他条件不变的情况下,将全铝微通道蒸发器替代铜铝翅片管蒸发器,对不同制冷剂充注量下微通道蒸发器房间空调器的性能以及微通道蒸发器制冷剂配液分布进行了红外成像试验研究.试验结果表明:微通道蒸发器房间空调器随着制冷剂充注量的增加,输入功率小幅上升0.27 kW,整机性能在充注量为2.3 kg时达到最优,制冷量和能效比呈现出先增大后减小的趋势,后者较前者由大变小的转变点有所滞后.红外成像结果同步反映出微通道蒸发器分液效果呈现出先变好后变差的趋势.与房间空调器原机铭牌参数相比,最佳充注量试验样机的制冷量增加2.50%,能效比高出2.84%,制冷剂充注量减少9.80%.
在一檯3HP分體落地式房間空調器殼體和風機等其他條件不變的情況下,將全鋁微通道蒸髮器替代銅鋁翅片管蒸髮器,對不同製冷劑充註量下微通道蒸髮器房間空調器的性能以及微通道蒸髮器製冷劑配液分佈進行瞭紅外成像試驗研究.試驗結果錶明:微通道蒸髮器房間空調器隨著製冷劑充註量的增加,輸入功率小幅上升0.27 kW,整機性能在充註量為2.3 kg時達到最優,製冷量和能效比呈現齣先增大後減小的趨勢,後者較前者由大變小的轉變點有所滯後.紅外成像結果同步反映齣微通道蒸髮器分液效果呈現齣先變好後變差的趨勢.與房間空調器原機銘牌參數相比,最佳充註量試驗樣機的製冷量增加2.50%,能效比高齣2.84%,製冷劑充註量減少9.80%.
재일태3HP분체락지식방간공조기각체화풍궤등기타조건불변적정황하,장전려미통도증발기체대동려시편관증발기,대불동제랭제충주량하미통도증발기방간공조기적성능이급미통도증발기제랭제배액분포진행료홍외성상시험연구.시험결과표명:미통도증발기방간공조기수착제랭제충주량적증가,수입공솔소폭상승0.27 kW,정궤성능재충주량위2.3 kg시체도최우,제랭량화능효비정현출선증대후감소적추세,후자교전자유대변소적전변점유소체후.홍외성상결과동보반영출미통도증발기분액효과정현출선변호후변차적추세.여방간공조기원궤명패삼수상비,최가충주량시험양궤적제랭량증가2.50%,능효비고출2.84%,제랭제충주량감소9.80%.
A micro-channel evaporator using aluminum fins was used as substitution for traditional evaporator using copper tubes with aluminum fins in a split type of 3 HP floor-standing room air condi-tioner.Keeping the fans and other conditions consistent,experimental studies on this modified room air conditioner performance with various refrigerant charge and different refrigerant distribution in the micro-channels were conducted and visualized with infrared thermographs.The results show that in the air conditioner using micro-channel evaporator,with the increase of refrigerant charge,there is a mi-nor increase in input power of 0.27 kW,and the tested unit has the best performance with a refrigerant charge of 2.3 kg.Meanwhile,the cooling capacity and EER (energy efficiency ratio)increase first then tend to decline,with the turning point of EER lagging behind that of cooling capacity.Corre-sponding infrared thermographs synchronously show the tendency of the effect of refrigerant distribu-tion in micro-channels,being from good to poor with the increase of refrigerant charge.In comparison with parameters on the nameplate of the original unit,the results reveal an increase of 2.50% and 2.84%in cooling capacity and EER,respectively,and a decrease of 9.80% in refrigerant charge in the modified unit.