变电站%施工%旁路母线%负荷转供
變電站%施工%徬路母線%負荷轉供
변전참%시공%방로모선%부하전공
substation%construction%bypass bus%load supply
变电站因施工需要双母带旁路母线全停时,为保证对用户持续供电,一般考虑用旁路母线转供一部分负荷。针对常规旁路母线转供存在的问题,如线路及设备潮流越限、继电保护失配等,提出选择适当位置拆断旁母,分段转供负荷的解决方案,在台州220 kV海门变电站的技术改造中得到了成功应用。
變電站因施工需要雙母帶徬路母線全停時,為保證對用戶持續供電,一般攷慮用徬路母線轉供一部分負荷。針對常規徬路母線轉供存在的問題,如線路及設備潮流越限、繼電保護失配等,提齣選擇適噹位置拆斷徬母,分段轉供負荷的解決方案,在檯州220 kV海門變電站的技術改造中得到瞭成功應用。
변전참인시공수요쌍모대방로모선전정시,위보증대용호지속공전,일반고필용방로모선전공일부분부하。침대상규방로모선전공존재적문제,여선로급설비조류월한、계전보호실배등,제출선택괄당위치탁단방모,분단전공부하적해결방안,재태주220 kV해문변전참적기술개조중득도료성공응용。
When the buses in double-bus with bypass faces full stop due to substation construction, the bypass buses are generally considered for partial power supply for the purpose of continuous power supply for users. Aiming at problems in power supply of bypass bus such as exceeded power flow of lines and equipment we well as mismatch of relay protection, the paper proposes a solution of bypass bus breaking and piecewise load supply, which is successfully applied in technical transformation of 220 kV Haimen substation.