高电压技术
高電壓技術
고전압기술
HIGH VOLTAGE ENGINEERING
2012年
11期
2863-2868
,共6页
陈澜%陈方东%赵雪松%卞星明%王黎明%关志成
陳瀾%陳方東%趙雪鬆%卞星明%王黎明%關誌成
진란%진방동%조설송%변성명%왕려명%관지성
电晕笼%电晕放电%电晕起始电压%雨滴%可听噪声%无线电干扰
電暈籠%電暈放電%電暈起始電壓%雨滴%可聽譟聲%無線電榦擾
전훈롱%전훈방전%전훈기시전압%우적%가은조성%무선전간우
corona cage%corona discharge%corona inception voltage%rain drop%audible noise%radio interference
除了导线表面的状态和成分,导线附近大气状况也是引起导线电晕特性变化的重要因素。可听噪声、无线电干扰是反映电晕特性变化的重要参数。通过自制淋雨装置,在小型电晕笼中对单根LGJ-400/50型实际输电导线进行干燥和淋雨情况下的电晕实验,并利用无线电干扰接收机和声级计检测电晕放电情况。实验结果显示,同等电压下LGJ-400/50型导线在大雨状况下,可听噪声和无线电干扰值明显增加,在干燥时的电晕起始电压附近有最大差值;施加电压超过干燥时电晕起始电压后,随施加电压的增长,干燥和淋雨情况下的可听噪声和无线电干扰值差值均减小。
除瞭導線錶麵的狀態和成分,導線附近大氣狀況也是引起導線電暈特性變化的重要因素。可聽譟聲、無線電榦擾是反映電暈特性變化的重要參數。通過自製淋雨裝置,在小型電暈籠中對單根LGJ-400/50型實際輸電導線進行榦燥和淋雨情況下的電暈實驗,併利用無線電榦擾接收機和聲級計檢測電暈放電情況。實驗結果顯示,同等電壓下LGJ-400/50型導線在大雨狀況下,可聽譟聲和無線電榦擾值明顯增加,在榦燥時的電暈起始電壓附近有最大差值;施加電壓超過榦燥時電暈起始電壓後,隨施加電壓的增長,榦燥和淋雨情況下的可聽譟聲和無線電榦擾值差值均減小。
제료도선표면적상태화성분,도선부근대기상황야시인기도선전훈특성변화적중요인소。가은조성、무선전간우시반영전훈특성변화적중요삼수。통과자제림우장치,재소형전훈롱중대단근LGJ-400/50형실제수전도선진행간조화림우정황하적전훈실험,병이용무선전간우접수궤화성급계검측전훈방전정황。실험결과현시,동등전압하LGJ-400/50형도선재대우상황하,가은조성화무선전간우치명현증가,재간조시적전훈기시전압부근유최대차치;시가전압초과간조시전훈기시전압후,수시가전압적증장,간조화림우정황하적가은조성화무선전간우치차치균감소。
Besides condition and material of electrode surface,the dielectric distributed around the surface of electrodes has significant influence on the corona discharge.Audible noise and radio influence are two key characteristics reflecting the change of corona discharge pattern.With the self-constructed water spray apparatus,corona experiments of a single LGJ-400/50conductor were carried out in a small corona cage under both fine and rainy conditions.Corona cage is an effective and economical means for duplicating corona progress in power transmission lines with lower voltage on the conductor in the cage.The corona characteristics were measured by an electromagnetic interference test receiver and a sound meter.The results show that the audible noise and radio influence in heavy rain circumstance significantly increases compared with that of fine weather condition under the same voltage.The difference between two circumstances reaches a peak at the corona inception voltage of dry condition.Since the voltage is higher than the corona inception voltage of dry condition,the audible noise and radio influence decreases with the increasing voltage in both rainy and dry circumstances.