ELECTRICAL MEASUREMENT & INSTRUMENTATION
2014年
6期
50-54
,共5页
潘荣超%刘念%甘德刚%杨琳%刘守豹%李顺%王利来%李建
潘榮超%劉唸%甘德剛%楊琳%劉守豹%李順%王利來%李建
반영초%류념%감덕강%양림%류수표%리순%왕리래%리건
500kV绝缘子串%零值绝缘子%电晕放电%电场分析%紫外检测
500kV絕緣子串%零值絕緣子%電暈放電%電場分析%紫外檢測
500kV절연자천%령치절연자%전훈방전%전장분석%자외검측
500kV insulator string%zero value insulator%corona discharge%electric field analysis%ultraviolet detection
由于绝缘子串中含有零值绝缘子可能会导致输电线路雷击跳闸事故,本文基于有限元法研究了绝缘子串中含零值绝缘子的电场分布,并结合紫外检测仪观测电晕放电综合研究绝缘子串的电晕放电情况。建立了绝缘子串的三维模型,考虑了绝缘串子中含有零值绝缘子时的情况,并对该模型进行了电场仿真,同时通过紫外检测技术观测了含零值绝缘子的绝缘子串电晕放电,而且电场分析结果与实测数据相符,零值绝缘子附近电场发生畸变,紫外观测数据显示零值绝缘子附近发生了电晕放电。零值绝缘子导致的电场畸变是零值绝缘子附近发生电晕放电的重要原因之一,该研究可用于高压输变电设备外绝缘状况紫外检测的诊断与评估。
由于絕緣子串中含有零值絕緣子可能會導緻輸電線路雷擊跳閘事故,本文基于有限元法研究瞭絕緣子串中含零值絕緣子的電場分佈,併結閤紫外檢測儀觀測電暈放電綜閤研究絕緣子串的電暈放電情況。建立瞭絕緣子串的三維模型,攷慮瞭絕緣串子中含有零值絕緣子時的情況,併對該模型進行瞭電場倣真,同時通過紫外檢測技術觀測瞭含零值絕緣子的絕緣子串電暈放電,而且電場分析結果與實測數據相符,零值絕緣子附近電場髮生畸變,紫外觀測數據顯示零值絕緣子附近髮生瞭電暈放電。零值絕緣子導緻的電場畸變是零值絕緣子附近髮生電暈放電的重要原因之一,該研究可用于高壓輸變電設備外絕緣狀況紫外檢測的診斷與評估。
유우절연자천중함유령치절연자가능회도치수전선로뢰격도갑사고,본문기우유한원법연구료절연자천중함령치절연자적전장분포,병결합자외검측의관측전훈방전종합연구절연자천적전훈방전정황。건립료절연자천적삼유모형,고필료절연천자중함유령치절연자시적정황,병대해모형진행료전장방진,동시통과자외검측기술관측료함령치절연자적절연자천전훈방전,이차전장분석결과여실측수거상부,령치절연자부근전장발생기변,자외관측수거현시령치절연자부근발생료전훈방전。령치절연자도치적전장기변시령치절연자부근발생전훈방전적중요원인지일,해연구가용우고압수변전설비외절연상황자외검측적진단여평고。
Insulator string containing zero value insulator may result in lightning trip-out accidents of transmission lines. Based on finite element method, the electric field distribution of insulator strings containing zero value insulator is studied. With the corona discharge data observed by the UV detector, corona discharge of the insulator string is also studied. With 3D model of the insulator string built and the insulator string with zero value insulator considered, the electric field distribution of the model is simulated. The corona discharge of the insulator string with zero value insulator has been observed using UV detection. The electric field analysis result agrees with the measured data, where the electric field near the zero value insulator is distorted and the corona discharge observed by ultraviolet detector occurs near the zero value insulator. Therefore, field distortion caused by zero value insulator is one of the important reasons for corona discharge near zero value insulator. The result can be used for external insulation diagnosis and assessment of high voltage power transmission equipment with UV detection.