分析了直流输电系统双极不平衡运行时地中直流电流对交流变压器励磁特性的影响。在三沪二回直流输电系统大功率调试期间,测试了受端直流接地极附近具有单相单柱旁轭铁心结构的交流变压器的运行性能。在双极平衡运行及不平衡运行的条件下,测量了变压器有载运行时的振动、噪声、油温、油色谱等参数,分析了变压器振动、噪声与双极运行不平衡度、主变的视在功率、油温等参数的相关性,以及直流偏磁对单相单柱旁轭的变压器运行性能的影响。测试结果表明,在双极不平衡运行期间,接地极附近交流站内变压器出现了不同程度的偏磁现象,但油温及油色谱等参数未出现异常,可以承受由此带来的偏磁影响。
分析瞭直流輸電繫統雙極不平衡運行時地中直流電流對交流變壓器勵磁特性的影響。在三滬二迴直流輸電繫統大功率調試期間,測試瞭受耑直流接地極附近具有單相單柱徬軛鐵心結構的交流變壓器的運行性能。在雙極平衡運行及不平衡運行的條件下,測量瞭變壓器有載運行時的振動、譟聲、油溫、油色譜等參數,分析瞭變壓器振動、譟聲與雙極運行不平衡度、主變的視在功率、油溫等參數的相關性,以及直流偏磁對單相單柱徬軛的變壓器運行性能的影響。測試結果錶明,在雙極不平衡運行期間,接地極附近交流站內變壓器齣現瞭不同程度的偏磁現象,但油溫及油色譜等參數未齣現異常,可以承受由此帶來的偏磁影響。
분석료직류수전계통쌍겁불평형운행시지중직류전류대교류변압기려자특성적영향。재삼호이회직류수전계통대공솔조시기간,측시료수단직류접지겁부근구유단상단주방액철심결구적교류변압기적운행성능。재쌍겁평형운행급불평형운행적조건하,측량료변압기유재운행시적진동、조성、유온、유색보등삼수,분석료변압기진동、조성여쌍겁운행불평형도、주변적시재공솔、유온등삼수적상관성,이급직류편자대단상단주방액적변압기운행성능적영향。측시결과표명,재쌍겁불평형운행기간,접지겁부근교류참내변압기출현료불동정도적편자현상,단유온급유색보등삼수미출현이상,가이승수유차대래적편자영향。
The impact of DC current in the earth on excitation characteristic of AC transformer under bi-polar asymmetric operation of HVDC power transmission system is analyzed. During the high-power commissioning of two circuit HVDC transmission system from the Three Gorges to Shanghai, the operating performance of single-phase AC transformer with three-limb core located near DC grounding pole at receiving end is measured and tested, and the relationship of vibration and noise of the transformer with such parameters as unbalance degree of bi-polar operation, apparent power of main transformer and oil temperature as well as the influence of DC-bias on operating performance of single-phase AC transformer with three-limb core are analyzed. Measurement and test results show that during bi-polar asymmetric operation of HVDC power transmission system the DC-bias phenomena to different extent appear in transformers inside the AC substation near the grounding pole, however the oil temperature and oil chromatograph are in normal condition, thus such a DC-bias phenomena are sustainable.