中国电机工程学报
中國電機工程學報
중국전궤공정학보
ZHONGGUO DIANJI GONGCHENG XUEBAO
2014年
18期
2906-2916
,共11页
李小强%伍小杰%耿乙文%张祺
李小彊%伍小傑%耿乙文%張祺
리소강%오소걸%경을문%장기
光伏逆变器%感性电网阻抗%广义奈奎斯特判据%d轴输出导纳%稳定性
光伏逆變器%感性電網阻抗%廣義奈奎斯特判據%d軸輸齣導納%穩定性
광복역변기%감성전망조항%엄의내규사특판거%d축수출도납%은정성
PV inverter%inductive grid impedance%generalized Nyquist stability criterion (GNC)%d channel output admittance%stability
许多情况下,电网并非理想的电压源,而是存在感性阻抗的弱电网。传统的光伏逆变器设计并没有考虑电网阻抗的影响,逆变器-电网级联系统阻抗不匹配容易导致逆变器的稳定性能降低,甚至不稳定。该文从阻抗的角度,分析L滤波和 LCL 滤波的光伏逆变器在感性电网阻抗下的稳定性,并分别对稳定判据和输出导纳模型展开研究。通过模型降阶和矩阵近似,简化广义奈奎斯特稳定判据对逆变器-电网级联系统的稳定性分析。借鉴直流电源导纳模型建立的方法,简化由闭环状态矩阵推导d轴输出导纳的计算过程。最后根据所提出的简化判据和建立的d轴输出导纳模型,分析两种滤波方式下级联系统的稳定性,并研究滤波器参数与对级联系统稳定裕度的影响。通过实验对所进行的稳定性分析进行了验证。
許多情況下,電網併非理想的電壓源,而是存在感性阻抗的弱電網。傳統的光伏逆變器設計併沒有攷慮電網阻抗的影響,逆變器-電網級聯繫統阻抗不匹配容易導緻逆變器的穩定性能降低,甚至不穩定。該文從阻抗的角度,分析L濾波和 LCL 濾波的光伏逆變器在感性電網阻抗下的穩定性,併分彆對穩定判據和輸齣導納模型展開研究。通過模型降階和矩陣近似,簡化廣義奈奎斯特穩定判據對逆變器-電網級聯繫統的穩定性分析。藉鑒直流電源導納模型建立的方法,簡化由閉環狀態矩陣推導d軸輸齣導納的計算過程。最後根據所提齣的簡化判據和建立的d軸輸齣導納模型,分析兩種濾波方式下級聯繫統的穩定性,併研究濾波器參數與對級聯繫統穩定裕度的影響。通過實驗對所進行的穩定性分析進行瞭驗證。
허다정황하,전망병비이상적전압원,이시존재감성조항적약전망。전통적광복역변기설계병몰유고필전망조항적영향,역변기-전망급련계통조항불필배용역도치역변기적은정성능강저,심지불은정。해문종조항적각도,분석L려파화 LCL 려파적광복역변기재감성전망조항하적은정성,병분별대은정판거화수출도납모형전개연구。통과모형강계화구진근사,간화엄의내규사특은정판거대역변기-전망급련계통적은정성분석。차감직류전원도납모형건립적방법,간화유폐배상태구진추도d축수출도납적계산과정。최후근거소제출적간화판거화건립적d축수출도납모형,분석량충려파방식하급련계통적은정성,병연구려파기삼수여대급련계통은정유도적영향。통과실험대소진행적은정성분석진행료험증。
In many cases, the grid is not ideal voltage source but a weak grid which contains inductive grid impedance. The influence of grid impedance is not considered in the conventional design of photovoltaic (PV) inverters. Impedance mismatch is likely to deteriorate the stability of the cascaded system of PV inverter and grid, even making the system unstable. From the perspective of the impedance, this paper analyzed the stability of PV inverter with L-filter and LCL-filter under the condition of inductive grid impedance, and the stability criterion and output admittance model were researched respectively. Through the model order reduction and matrix approximating, the stability analysis of inverter cascaded with grid which was usually complemented based on the generalized Nyquist stability criterion (GNC) is simplified. Drawing on the method in which the admittance models of the DC power are built, the calculation process of the d channel output admittance which was usually derived from the closed-loop state matrices is simplified. According to the proposed simplified criterion and the established d channel output admittance model, the stability of PV inverter cascaded with grid was analyzed, and the influence of filter parameters on stability margin of the cascaded system was studied. Experimental results validate the proposed theoretical stability analysis.