高速铁路客站%雨棚%金属屋面%抗风揭
高速鐵路客站%雨棚%金屬屋麵%抗風揭
고속철로객참%우붕%금속옥면%항풍게
high-speed railway station%canopy%metal roof%wind blowing-off
新型高速铁路客站雨棚大多采用直立锁边压型金属板屋面,由于直立锁边金属屋面的计算和试验方法尚不成熟,近年出现多起金属屋面被风吹落的现象。为了高速铁路运营安全,保证金属屋面质量,提高抗风揭能力,必须要强化施工图设计,把好原材料进场关,加强过程控制,规范验收工作,同时要加强风揭试验的验证。西安北站雨棚屋面的风揭试验表明,屋面抗风揭能力最薄弱的地方在支座和屋面板的咬口锁边处,通过在支座和屋面板的咬扣锁边位置增加抗风夹具,对薄弱处进行加强设计能够显著提高屋面的抗风揭能力,为提高直立锁边屋面抗风揭能力指出了方向,同时也表明抗风揭试验在金属屋面设计过程中的紧迫性和必要性。
新型高速鐵路客站雨棚大多採用直立鎖邊壓型金屬闆屋麵,由于直立鎖邊金屬屋麵的計算和試驗方法尚不成熟,近年齣現多起金屬屋麵被風吹落的現象。為瞭高速鐵路運營安全,保證金屬屋麵質量,提高抗風揭能力,必鬚要彊化施工圖設計,把好原材料進場關,加彊過程控製,規範驗收工作,同時要加彊風揭試驗的驗證。西安北站雨棚屋麵的風揭試驗錶明,屋麵抗風揭能力最薄弱的地方在支座和屋麵闆的咬口鎖邊處,通過在支座和屋麵闆的咬釦鎖邊位置增加抗風夾具,對薄弱處進行加彊設計能夠顯著提高屋麵的抗風揭能力,為提高直立鎖邊屋麵抗風揭能力指齣瞭方嚮,同時也錶明抗風揭試驗在金屬屋麵設計過程中的緊迫性和必要性。
신형고속철로객참우붕대다채용직립쇄변압형금속판옥면,유우직립쇄변금속옥면적계산화시험방법상불성숙,근년출현다기금속옥면피풍취락적현상。위료고속철로운영안전,보증금속옥면질량,제고항풍게능력,필수요강화시공도설계,파호원재료진장관,가강과정공제,규범험수공작,동시요가강풍게시험적험증。서안북참우붕옥면적풍게시험표명,옥면항풍게능력최박약적지방재지좌화옥면판적교구쇄변처,통과재지좌화옥면판적교구쇄변위치증가항풍협구,대박약처진행가강설계능구현저제고옥면적항풍게능력,위제고직립쇄변옥면항풍게능력지출료방향,동시야표명항풍게시험재금속옥면설계과정중적긴박성화필요성。
The standing seam pressed metal roof is used mostly for canopy of new high-speed railway station.Because the calculation and test method of standing seam metal roof is not mature,many situations metal roof blows off occur in re-cent years.In order to ensure the safe operation of high-speed railway and metal roof quality,improve the wind-resist-ance capacity,it is necessary to strengthen the construction drawing design,use good raw material,strengthen the process control,normalize acceptance work and strengthen verification of wind blowing-off test.The wind blowing-off test result of canopy roof of Xi'an North Railway Station shows the seaming lockrand place between support and roof plate is the weakest places against wind.It can remarkably improve the roof wind-resistance capacity to install wind-resistance clamp at the seaming lockrand place between support and roof plate,which points out the direction for improvement of wind-resistance ability of standing seam roof.At the same time also shows wind blowing-off test is urgent and necessary in the design of metal roof.