钟笑拳%周力行%赵宪%邓慧都%刘涛%彭杰
鐘笑拳%週力行%趙憲%鄧慧都%劉濤%彭傑
종소권%주역행%조헌%산혜도%류도%팽걸
GIS%隔离开关%VFTO%金属氧化物避雷器%ATP-EMTP
GIS%隔離開關%VFTO%金屬氧化物避雷器%ATP-EMTP
GIS%격리개관%VFTO%금속양화물피뢰기%ATP-EMTP
GIS%disconnector%VFTO%metal oxide arrester%ATP-EMTP
随着全封闭式气体绝缘变电站( GIS)的广泛引用,由隔离开关操作引起的特快速暂态过电压( VFTO)造成的事故频发。金属氧化物避雷器在限制过电压方面应用广泛,总结了目前应用的4种避雷器模型,运用电磁暂态程序ATP-EMTP分别建立仿真模型,以国内某1000 kVGIS电站为研究背景,分别模拟了在这4种避雷器模型作用下由隔离开关分闸操作引起特快速暂态过电压,得到了过电压的时域波形图,再运用MATLAB对时域波形进行变换得到VFTO的幅频特性图。对比了4种避雷器模型对VFTO的抑制效果,其中第4种模型更加精确,对过电压幅值、频率抑制效果最好。
隨著全封閉式氣體絕緣變電站( GIS)的廣汎引用,由隔離開關操作引起的特快速暫態過電壓( VFTO)造成的事故頻髮。金屬氧化物避雷器在限製過電壓方麵應用廣汎,總結瞭目前應用的4種避雷器模型,運用電磁暫態程序ATP-EMTP分彆建立倣真模型,以國內某1000 kVGIS電站為研究揹景,分彆模擬瞭在這4種避雷器模型作用下由隔離開關分閘操作引起特快速暫態過電壓,得到瞭過電壓的時域波形圖,再運用MATLAB對時域波形進行變換得到VFTO的幅頻特性圖。對比瞭4種避雷器模型對VFTO的抑製效果,其中第4種模型更加精確,對過電壓幅值、頻率抑製效果最好。
수착전봉폐식기체절연변전참( GIS)적엄범인용,유격리개관조작인기적특쾌속잠태과전압( VFTO)조성적사고빈발。금속양화물피뢰기재한제과전압방면응용엄범,총결료목전응용적4충피뢰기모형,운용전자잠태정서ATP-EMTP분별건립방진모형,이국내모1000 kVGIS전참위연구배경,분별모의료재저4충피뢰기모형작용하유격리개관분갑조작인기특쾌속잠태과전압,득도료과전압적시역파형도,재운용MATLAB대시역파형진행변환득도VFTO적폭빈특성도。대비료4충피뢰기모형대VFTO적억제효과,기중제4충모형경가정학,대과전압폭치、빈솔억제효과최호。
With the wide use of the all closed gas insulate substation (GIS), the very fast transient overvoltage ( VFTO) caused by the operations of disconnectors has triggered more and more accidents. The metal oxide arrest-er has been widely applied in terms of limiting over voltage. This paper summarizes the current application of the four types of surge arrester model, and builds the corresponding electromagnetic transient program ATP-EMTP sim-ulation models using. Taking a 1000kV GIS in China as a research backgroudne, the very fast transient overvoltage caused by the operations of disconnectors by the action of the four surge arrester model is simulated, acquire the o-ver voltage waveform in the time domain is acquired, amplitude-freequency charateristic diagram is then transfor-ming the time domain waveform using MATLAB. The inhibitory effects of the four types of surge arrester model on VFTO are compared. The results show that the fourth model is more accurate, it can better suppress the amplitude and frequency of the overvoltage.