零序电流差动保护对接地故障灵敏度高,动作电流与变压器调压分接头无关,受励磁涌流影响小,原理简单等优点,在超高压自耦变压器保护上得到广泛应用。但零序电流差动保护由于反应自耦变压器三侧零序电流的相量和而动作,受电流互感器饱和影响较大,不易整定,在区外故障切除时常常导致保护的误动。据此提出“基于零序电流的超高压自耦变压器相位比较纵联保护方案”。该方案比较自耦变压器两侧保护处零序电流相位,根据相位相同或相反作为故障判据来区分自耦变压器内部故障或外部故障。动模试验数据和数字仿真验证结果表明,该方案具有对超高压自耦变压器接地故障灵敏度高,选择性好,能够正确反应自耦变压器各种轻微匝间故障,保护判据均不受零序电流非周期分量和故障侧电流互感器(CT)饱和深度的影响等优点。
零序電流差動保護對接地故障靈敏度高,動作電流與變壓器調壓分接頭無關,受勵磁湧流影響小,原理簡單等優點,在超高壓自耦變壓器保護上得到廣汎應用。但零序電流差動保護由于反應自耦變壓器三側零序電流的相量和而動作,受電流互感器飽和影響較大,不易整定,在區外故障切除時常常導緻保護的誤動。據此提齣“基于零序電流的超高壓自耦變壓器相位比較縱聯保護方案”。該方案比較自耦變壓器兩側保護處零序電流相位,根據相位相同或相反作為故障判據來區分自耦變壓器內部故障或外部故障。動模試驗數據和數字倣真驗證結果錶明,該方案具有對超高壓自耦變壓器接地故障靈敏度高,選擇性好,能夠正確反應自耦變壓器各種輕微匝間故障,保護判據均不受零序電流非週期分量和故障側電流互感器(CT)飽和深度的影響等優點。
령서전류차동보호대접지고장령민도고,동작전류여변압기조압분접두무관,수려자용류영향소,원리간단등우점,재초고압자우변압기보호상득도엄범응용。단령서전류차동보호유우반응자우변압기삼측령서전류적상량화이동작,수전류호감기포화영향교대,불역정정,재구외고장절제시상상도치보호적오동。거차제출“기우령서전류적초고압자우변압기상위비교종련보호방안”。해방안비교자우변압기량측보호처령서전류상위,근거상위상동혹상반작위고장판거래구분자우변압기내부고장혹외부고장。동모시험수거화수자방진험증결과표명,해방안구유대초고압자우변압기접지고장령민도고,선택성호,능구정학반응자우변압기각충경미잡간고장,보호판거균불수령서전류비주기분량화고장측전류호감기(CT)포화심도적영향등우점。
Zero-sequence-current-differential-protection-for-grounding-fault-has-the-advantages-of-high-sensitivity,-action-current’s-independence-with-transformer-tap-joint,-small-influence-from-inrush-current,-and-principle-simplicity.-It-is-widely-used-in-the-area-of-UHV-autotransformer-protection.-However,-the-zero-sequence-current-differential-protection-operates-due-to-responding-to-the-phase-sum-of-zero-sequence-current-in-three-sides-of-autotransformer,-which-is-badly-influenced-by-the-saturation-of-current-transformer-and-hard-to-set-the-threshold.-In-the-external-fault,-it-will-lead-to-mal-operation.-Based-on-this,-a-new-auto-transformer-pilot-protection-scheme-based-on-the-zero-sequence-current-phase-comparison-is-proposed.-The-fault-direction-can-be-determined-by-comparing-the-phase-shift-between-zero-sequence-current-of-high-voltage-side,-medium-voltage-side-and-the-reference-current.-So-the-internal-fault-and-external-fault-can-be-discriminated.-The-results-of-dynamic-simulation-experiment-and-digital-simulation-shows-that-the-proposed-method-can-detect-turn-to-ground-and-turn-to-turn-fault-with-high-sensitivity-and-good-selectivity.-Besides,-the-protection-criterion-is-not-affected-both-by-the-non-periodic-component-of-zero-sequence-current-and-saturation-level-of-fault-side-current-transformer-(CT).