同塔双回输电线路采用逆相序排列方式可以很好地解决三相电流不平衡的问题,而同塔四回输电线路的三相不平衡问题要复杂得多,不能简单地采用逆相序排列方式。为此,首先分析了同塔四回输电线路三相不平衡产生的原因,然后利用 PSCAD/EMTDC软件对同塔四回输电线路不同的相序排列方式进行了仿真研究;搭建了基于Multiple-Run模块的同塔四回输电线路最优相序筛选模型,给出了相应的程序流程图,通过该模型可以计算不同目标函数下的最优相序。最后以广东揭阳电网某220 kV和500 kV同塔四回输电线路三相电流不平衡问题为例,利用提出的模型和方法,推荐了最优相序改造方案;该方案已被采纳实施,取得了较好的效果。
同塔雙迴輸電線路採用逆相序排列方式可以很好地解決三相電流不平衡的問題,而同塔四迴輸電線路的三相不平衡問題要複雜得多,不能簡單地採用逆相序排列方式。為此,首先分析瞭同塔四迴輸電線路三相不平衡產生的原因,然後利用 PSCAD/EMTDC軟件對同塔四迴輸電線路不同的相序排列方式進行瞭倣真研究;搭建瞭基于Multiple-Run模塊的同塔四迴輸電線路最優相序篩選模型,給齣瞭相應的程序流程圖,通過該模型可以計算不同目標函數下的最優相序。最後以廣東揭暘電網某220 kV和500 kV同塔四迴輸電線路三相電流不平衡問題為例,利用提齣的模型和方法,推薦瞭最優相序改造方案;該方案已被採納實施,取得瞭較好的效果。
동탑쌍회수전선로채용역상서배렬방식가이흔호지해결삼상전류불평형적문제,이동탑사회수전선로적삼상불평형문제요복잡득다,불능간단지채용역상서배렬방식。위차,수선분석료동탑사회수전선로삼상불평형산생적원인,연후이용 PSCAD/EMTDC연건대동탑사회수전선로불동적상서배렬방식진행료방진연구;탑건료기우Multiple-Run모괴적동탑사회수전선로최우상서사선모형,급출료상응적정서류정도,통과해모형가이계산불동목표함수하적최우상서。최후이엄동게양전망모220 kV화500 kV동탑사회수전선로삼상전류불평형문제위례,이용제출적모형화방법,추천료최우상서개조방안;해방안이피채납실시,취득료교호적효과。
It is able to well solve problem of three phase current unbalance by using inverse phase sequence arrangement for double circuit power transmission line on the same tower while it is more complicated for three phase unbalance for quadrup-le circuit power transmission line on the same tower which means unable to simply use inverse phase sequence arrangement way. Therefore,cause for three phase unbalance of quadruple circuit power transmission line on the same tower was ana-lyzed and simulation studies on different phase sequence arrangement ways were conducted by using PSCAD/EMTDC soft-ware. Optimal phase sequence screening model for quadruple circuit power transmission line on the same tower based on Multiple-Run module was established by which optimal phase sequence under different target functions were able to be calcu-lated. Meanwhile,relevant program flow diagram was proposed. Taking three phase current unbalance of some 220 kV and 500 kV quadruple circuit power transmission lines on same towers in Guangdong Jieyang power grid as examples and using proposed model and method,optimal phase sequence transform scheme was recommended which was adopted and implemen-ted and proved to be of good effectiveness.