针对四川什邡500 kV变电站SVC电抗器周围电缆发热问题,进行了现场测试,复核了相关规范和设计方案,对相关原因进行分析,结合电磁场仿真计算和验证测试,提出相应的改进措施和SVC设计的注意事项。
針對四川什邡500 kV變電站SVC電抗器週圍電纜髮熱問題,進行瞭現場測試,複覈瞭相關規範和設計方案,對相關原因進行分析,結閤電磁場倣真計算和驗證測試,提齣相應的改進措施和SVC設計的註意事項。
침대사천십방500 kV변전참SVC전항기주위전람발열문제,진행료현장측시,복핵료상관규범화설계방안,대상관원인진행분석,결합전자장방진계산화험증측시,제출상응적개진조시화SVC설계적주의사항。
Aiming at the cable heating around the SVC reactor of Sichuan Shifang 500 kV Substation,a field test is carried out. The related specifications and design schemes are rechecked and the causes analyzed. According to the simulation calculation and verification test of the electromagnetic field, some improvement measures and precautions for the design of SVC are put forward in the this paper,which can be used as a reference for the designers in the future.