双馈感应发电机( DFIG)采用转子撬棒( Crowbar)进行低电压穿越保护时,须向电网吸收大量的无功功率,不利于故障过程中电网电压恢复。文中在双馈风电场中加入静止同步补偿器( STATCOM),用以补偿Crowbar动作后DFIG异步运行时对电网的无功需求。通过不同程度电压跌落下风电场动态仿真进行验证,结果表明电网电压跌落严重时STATCOM的无功补偿效果明显,电网故障中DFIG还能向电网提供一定出力,维持电网稳定运行;与只投入Crowbar的情况相比,同时加入STATCOM和Crowbar不会对DFIG各分量产生冲击;电压跌落轻微时DFIG可通过自身的变流器调节实现低电压穿越,投入Crowbar和STATCOM反而会加剧系统的振荡。
雙饋感應髮電機( DFIG)採用轉子撬棒( Crowbar)進行低電壓穿越保護時,鬚嚮電網吸收大量的無功功率,不利于故障過程中電網電壓恢複。文中在雙饋風電場中加入靜止同步補償器( STATCOM),用以補償Crowbar動作後DFIG異步運行時對電網的無功需求。通過不同程度電壓跌落下風電場動態倣真進行驗證,結果錶明電網電壓跌落嚴重時STATCOM的無功補償效果明顯,電網故障中DFIG還能嚮電網提供一定齣力,維持電網穩定運行;與隻投入Crowbar的情況相比,同時加入STATCOM和Crowbar不會對DFIG各分量產生遲擊;電壓跌落輕微時DFIG可通過自身的變流器調節實現低電壓穿越,投入Crowbar和STATCOM反而會加劇繫統的振盪。
쌍궤감응발전궤( DFIG)채용전자효봉( Crowbar)진행저전압천월보호시,수향전망흡수대량적무공공솔,불리우고장과정중전망전압회복。문중재쌍궤풍전장중가입정지동보보상기( STATCOM),용이보상Crowbar동작후DFIG이보운행시대전망적무공수구。통과불동정도전압질락하풍전장동태방진진행험증,결과표명전망전압질락엄중시STATCOM적무공보상효과명현,전망고장중DFIG환능향전망제공일정출력,유지전망은정운행;여지투입Crowbar적정황상비,동시가입STATCOM화Crowbar불회대DFIG각분양산생충격;전압질락경미시DFIG가통과자신적변류기조절실현저전압천월,투입Crowbar화STATCOM반이회가극계통적진탕。
Doubly fed induction generator ( DFIG) uses a rotor crowbar ( Crowbar) for low voltage ride through protection,and needs to absorbe considerable reactive power from grid, which is not conducive to the grid fault restoration process. In this paper, the STATCOM are added to the wind farm with DFIG,and it is used for satisfying the DFIG?S demand of reactive power from the power grid after the start the Crowbar circuit. According to the dynamic response of the DFIG in different degree of voltage drop simulation results, the effect of STATCOM on reactive power compensation is obvious and DFIG can provide amount active power to the grid when the grid voltage drops seriously. Compared with the crowbar circuit, adding STATCOM device and Crowbar circuit do not have an impact on DFIG? components. when the voltage drop isn?t so serious, DFIG can achieve low voltage ride through by it?s own low voltage ride through capability, and external crowbar circuit and STATCOM device can increases system?s oscillatory.