电力系统保护与控制
電力繫統保護與控製
전력계통보호여공제
POWER SYSTM PROTECTION AND CONTROL
2014年
19期
62-67
,共6页
金恩淑%陈亚潇%扈佃爱%江坤
金恩淑%陳亞瀟%扈佃愛%江坤
금은숙%진아소%호전애%강곤
广域电流差动保护%动作电流%制动电流%电容电流%补偿精度
廣域電流差動保護%動作電流%製動電流%電容電流%補償精度
엄역전류차동보호%동작전류%제동전류%전용전류%보상정도
wide-area current differential protection%operating current%braking current%capacitive current%compensation precision
为避免广域电流差动保护受电容电流影响而误动的情况发生,通过对传统电流差动保护进行改进,提出一种不受电容电流影响的广域电流差动保护算法。利用微分方程计算出各线路上的电容电流,采用修正的差动电流对暂态和稳态电容电流进行有效补偿,即在传统差动电流基础上减去计算出的电容电流以使电流差动保护不再受电容电流的影响。利用PSCAD仿真实验将改进的广域电流差动保护与传统原理的电流差动保护进行了比较。结果表明,该保护不受电容电流影响,外部故障时可靠不动作,验证了此保护算法的可行性和有效性。
為避免廣域電流差動保護受電容電流影響而誤動的情況髮生,通過對傳統電流差動保護進行改進,提齣一種不受電容電流影響的廣域電流差動保護算法。利用微分方程計算齣各線路上的電容電流,採用脩正的差動電流對暫態和穩態電容電流進行有效補償,即在傳統差動電流基礎上減去計算齣的電容電流以使電流差動保護不再受電容電流的影響。利用PSCAD倣真實驗將改進的廣域電流差動保護與傳統原理的電流差動保護進行瞭比較。結果錶明,該保護不受電容電流影響,外部故障時可靠不動作,驗證瞭此保護算法的可行性和有效性。
위피면엄역전류차동보호수전용전류영향이오동적정황발생,통과대전통전류차동보호진행개진,제출일충불수전용전류영향적엄역전류차동보호산법。이용미분방정계산출각선로상적전용전류,채용수정적차동전류대잠태화은태전용전류진행유효보상,즉재전통차동전류기출상감거계산출적전용전류이사전류차동보호불재수전용전류적영향。이용PSCAD방진실험장개진적엄역전류차동보호여전통원리적전류차동보호진행료비교。결과표명,해보호불수전용전류영향,외부고장시가고불동작,험증료차보호산법적가행성화유효성。
To avoid the circumstances that the maloperation currently occurs when the wide-area current differential protection is influenced by the capacitive current, this paper improves the traditional current differential protection and puts forward a way to calculate the wide-area current differential protection that is not affected by capacitive current. We use differential equation to calculate the capacitive current on different circuits, and by using amendatory differential current, we make efficient compensation for fault transient current and steady capacitive current. That is to guarantee current differential protection against the influence from capacitive current, we subtract the calculated capacitive current from the traditional differential current. The PSCAD simulation experiment compares this protection with the traditional current differential protection. It turns out that this protection is not affected by capacitive current, and has no maloperation through external failure, which verifies the feasibility and effectiveness of this protective calculation.