针对并网点电压不平衡且同时含有5次、7次谐波电压的电网条件,文中利用串联网侧变换器和并联网侧变换器的协调控制以及正向同步旋转轴系下的比例积分-双频谐振(PI-DFR)控制器,提出了基于串联网侧变换器的双馈风电系统在不平衡且谐波畸变电网电压下的改进控制策略;在实现了定转子电流平衡无畸变、发电机输出功率和电磁转矩无波动的同时,亦消除了系统输出有功功率的2倍和6倍频波动。此外,还提出了考虑并联网侧变换器电流容量时参考电流指令在其电流最大值下的分配原则及分配后的参考电流指令。对一台2 MW基于串联网侧变换器的双馈风电系统在不平衡且谐波畸变电网电压下的仿真分析,验证了所提控制策略及并联网侧变换器参考电流指令分配原则的正确性。
針對併網點電壓不平衡且同時含有5次、7次諧波電壓的電網條件,文中利用串聯網側變換器和併聯網側變換器的協調控製以及正嚮同步鏇轉軸繫下的比例積分-雙頻諧振(PI-DFR)控製器,提齣瞭基于串聯網側變換器的雙饋風電繫統在不平衡且諧波畸變電網電壓下的改進控製策略;在實現瞭定轉子電流平衡無畸變、髮電機輸齣功率和電磁轉矩無波動的同時,亦消除瞭繫統輸齣有功功率的2倍和6倍頻波動。此外,還提齣瞭攷慮併聯網側變換器電流容量時參攷電流指令在其電流最大值下的分配原則及分配後的參攷電流指令。對一檯2 MW基于串聯網側變換器的雙饋風電繫統在不平衡且諧波畸變電網電壓下的倣真分析,驗證瞭所提控製策略及併聯網側變換器參攷電流指令分配原則的正確性。
침대병망점전압불평형차동시함유5차、7차해파전압적전망조건,문중이용천련망측변환기화병련망측변환기적협조공제이급정향동보선전축계하적비례적분-쌍빈해진(PI-DFR)공제기,제출료기우천련망측변환기적쌍궤풍전계통재불평형차해파기변전망전압하적개진공제책략;재실현료정전자전류평형무기변、발전궤수출공솔화전자전구무파동적동시,역소제료계통수출유공공솔적2배화6배빈파동。차외,환제출료고필병련망측변환기전류용량시삼고전류지령재기전류최대치하적분배원칙급분배후적삼고전류지령。대일태2 MW기우천련망측변환기적쌍궤풍전계통재불평형차해파기변전망전압하적방진분석,험증료소제공제책략급병련망측변환기삼고전류지령분배원칙적정학성。
In view of the grid condition that the voltage at the grid connection point is unbalanced and contains fifth-and seventh-order harmonics,this paper presents an improved control strategy for a doubly-fed wind power system with series grid-side converter (SGSC) by coordinated control of the SGSC and parallel grid-side converter (PGSC).A proportional-integral double frequency resonance(PI-DFR)controller in the positive synchronous rotating reference frame during network unbalance and fifth-and seventh-order harmonics distortion is investigated.With the proposed control strategy,the stator and rotor currents are balanced distortion free and the generator”s output power and electromagnetic torque pulsation free.While two-fold and six-fold frequency pulsations in the total active power output of the doubly-fed wind power system can be restrained.In addition,the allocation principles of the reference currents in the PGSC are studied when considering the current capacity of PGSC.Finally,simulation results of a 2 MW doubly-fed wind power system with SGSC under unbalanced and distorted grid voltage condition are used to verify the proposed control strategy and allocation principles of PGSC”s reference currents.